Wire control signals to the unit’s low
voltage terminal block located in the
controls compartment.

If any factory installed wiring must be
replaced, use a minimum 105°C type AWM
insulated conductors.

Variable Speed Compressors
Variable speed compressors with VFD
speed control are available on 55, 65 and 75-
140 ton units. Variable speed compressors
should not be operated outside the factory
determined frequency range. The factory
determined compressor VFD frequency
range is given below in Table 7.

Table 7 - Variable Speed Compressor VFD

Frequency Range

Model (RN-)

Compressor VFD

Range (Hz)

208V and 230 V Units

055, 065 & 075-140

35-60 Hz

460V and 575V Units

055, 065, 075, 090,

120, 130

35-75 Hz

105, 140

35-60 Hz













Thermostat Control Wiring
If a thermostat is used for unit control,
thermostat should be located on an inside
wall 4-5 feet above the floor where it will
not be subjected to drafts, sun exposure, or
heat from electrical fixtures of appliances.
Control wiring must deliver adequate
voltage to components to assure proper
operation. Control voltage returning from
controller circuit must be a minimum of 21
VAC. To assure proper wiring use the
following chart to determine the allowable
wiring distances.

Table 8 - Control Wiring

Wire Size (Stranded)
- Copper Conductors
Only

Total Wire Distance
Allowable

20 AWG

200 ft

18 AWG

350 ft

16 AWG

500 ft

14 AWG

750 ft

12 AWG

1250 ft


Rotation must be checked on all
MOTORS AND COMPRESSORS of
three phase units. Supply fan,
exhaust

fan,

return

fan,

and

condenser fan motors should all be
checked by a qualified service
technician at startup and any wiring
alteration should only be made at the
unit power connection.

CAUTION


Scroll compressors are directional
and will be damaged by operation in
the wrong direction. Low pressure
switches on compressors have been
disconnected after factory testing.
Rotation should be checked by a
qualified service technician at startup
using suction and discharge pressure
gauges and any wiring alteration
should only be made at the unit
power connection.

CAUTION



No variable speed compressor shall
operate below 35 Hz. Operating
variable speed compressors outside
the frequency range specified in this
manual voids all warranties and may
result in compressor failure.

CAUTION