IGNITION CONTROL CHECKOUT PROCEDURE

NO

IS 24v AVAILABLE

AT

IGNITION CONTROL ?

NO

CORRECTION NECESSARY

IS 24v AVAILABLE AT

GAS VALVE ?

YES

YES

IS FLAME SENSOR

CABLE SECURELY

ATTACHED ?

NO

NO

YES

IS SENSOR

CERAMIC CRACKED

OR BROKEN ?

NO

IS SENSOR

LOCATED IN

BURNER FLAME ?

YES

REPLACE

SENSOR

ASSEMBLY

NO

YES

CHECK SENSOR

CABLE

CONTINUITY

NOT
O.K.

REPLACE CABLE

O.K.

REPLACE

IGNITION

CONTROL

CHECK GAS VALVE

WIRING FOR PROPER,

TIGHT CONNECTIONS

YES

IS GAS PRESSURE

PER MANUFACTURE'S

SPECIFICATIONS ?

YES

IS SPARK GAP

LOCATED IN GAS

STREAM ?

NO

SPARK IS PRESENT

BUT BURNER

WILL NOT LIGHT

NO

CHECK GAS SUPPLY

FOR OBSTRUCTIONS

OR CLOSED VALVES

REPLACE

GAS VALVE

NO

IS IGNITION CONTROL

LOCKED OUT ?

CHECK TRANSFORMER
AND / OR THERMOSTAT

FOR MALFUNCTION

REPLACE AS NECESSARY.

REPLACE OPEN LIMIT

YES

YES

NO

RESET BY TURNING

THE THERMOSTAT

TO "OFF"

THEN BACK TO HEAT

IS SPARK GAP 0.10 ?

YES

REGAP TO 0.10

IS ELECTRODE

CERAMIC CRACKED

OR BROKEN ?

NO

YES

NO

REPLACE ELECTRODE

IS HIGH VOLTAGE CABLE

FIRMLY ATTACHED AND

IN GOOD CONDITION ?

YES

NO

REPLACE CONTROL

REPLACE CABLE

OR CORRECT
CONNECTION

NO SPARK

ON

CALL FOR HEAT

IS THERE 24v AT

IGNITION CONTROL ?

SHOULD BE CLOSED

CHECK FUSES

WARNING: ALL SAFETY PRECAUTIONS MUST BE FOLLOWED WHEN EVALUATING

THE IGNITION CONTROL SYSTEM ON GAS HEATING UNITS.