22

* 380, 400, and 416 volt dryers are built 4-wire only. Customer must contact factory to special order 3-wire systems.

IMPORTANT: Figures shown are for non-reversing models only. For reversing models contact the

factory.

IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is

affixed to the left side panel area behind the top control (access) door. In the case of
208 VAC or 230/240 VAC, the supply voltage must match the electric service
specifications of the data label exactly.

IMPORTANT: The wire size must be properly sized to handle the related current.

WARNING: 208 VAC AND 230/240 VAC ARE NOT THE SAME. Any damage done to dryer

components due to improper voltage connections will automatically VOID THE
WARRANTY.

NOTE: Manufacturer reserves the right to make changes in specifications at any time without notice or

obligation.

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

IMPORTANT:

NOTES: A.

B.


C.

208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering,
specify
exact voltage.

When fuses are used they must be dual element, time delay, current

limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse value,
by applying either local and/or National Electrical Codes to listed
appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) motor curve type ONLY.
For others, calculate/verify correct breaker size according to appliance
amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3Ø) dryers must be 3-pole type.

SERVICE

VOLTAGE

PHASE

WIRE

SERVICE

APPROX.

AMP DRAW

CIRCUIT

BREAKER

60 Hz

50 Hz

120

2

12.0

---

20

208

2

7.4

---

15

230/240

2

6.5

4.9

15

208

3

3.0

---

15

230/240

3

3.1

3.6

15

380-400

4*

---

2.2

15

416

4*

---

2.3

15

460/480

3

2.1

---

15