Technical specifications, Electricity supply, Heat pump – DE DIETRICH AWHP MIT-IN iSystem User Manual

Page 30: 6 technical specifications, 1 technical specifications

Advertising
background image

6 Technical specifications

6.1

Technical specifications

6.1.1.

Electricity supply

230 V AC (+/- 10%) - 50 Hz

6.1.2.

Heat pump

Conditions of use:

4

Limit operating temperatures in Hot mode:

-

Water: +18 °C / +55 °C

-

Outside air:

-15 °C / +35 °C (AWHP 6 MR, 8 MR)

-20 °C / +35 °C (AWHP 11-27)

4

Limit operating temperatures in Cooling mode:

-

Water: +7 °C / +25 °C

-

Outside air: +15 °C / +40 °C (At less than 18°C, it is necessary

to use the HK24 insulation kit option)

4

Maximum operating pressure: 3 bar

AWHP

6 MR

8 MR

11 MR 11 TR

14 MR 14 TR

16 MR 16 TR

22 TR

27 TR

Calorific output -
A7/W35

(1)

kW

6.0

8.5

10.9

10.9

13.7

13.7

15.7

15.7

19.4

24.4

COP hot - A7/
W35

(1)

4.00

4.10

4.23

4.23

4.03

4.03

3.90

3.90

3.94

3.90

Absorbed

electrical power -
A7/W35

(1)

kWe

1.5

2.1

2.6

2.6

3.4

3.4

4.03

4.03

4.9

6.3

Nominal

amperage - A7/
W35

(1)

A

6.8

9.2

11.2

6.7

14.8

8.8

17.6

10.1

12.3

15.6

Calorific output -
A2/W35

(2)

kW

4.4

5.9

7.6

7.6

10.3

10.3

10.4

10.4

11.62

14.7

COP hot - A2/
W35

(2)

3.12

3.12

3.10

3.10

3.10

3.10

3.10

3.10

3.01

3.10

Absorbed

electrical power -
A2/W35

(2)

kWe

1.41

1.89

2.45

2.45

3.32

3.32

3.35

3.35

3.86

4.74

(1) Hot mode: Outside air temperature +7 °C, Water temperature at the outlet +35 °C. Performances in line with EN 14511-2.

(2) Hot mode: Outside air temperature +2 °C, Water temperature at the outlet +35 °C. Performances in line with EN 14511-2.

(3) Cooling mode: Outside air temperature +35 °C, Water temperature at the outlet +18 °C. Performances in line with EN 14511-2

(4) 5 m from the appliance, free field.

(5) Test conducted in accordance with the standard NF EN 12102

6. Technical specifications

AWHP MIT-IN iSystem

29

09/01/13 - 300027618-001-02

Advertising