Flowline DL34 EchoPod User Manual
Page 15

31 MAR 11
EchoPod
15 of 29
Rev B
MN204210
Switch Hysteresis/Dead band
This feature allows you to select a hysteresis or dead band for the
remaining high and/or low alarms.
o Options for Hysteresis/Dead band – No Hysteresis, ¼”, ½”,
1”, 2”, ½ cm, 1cm, 2 cm, 5 cm or Not Applicable.
o High Alarms – Relay activates above set point. Relay will
deactivate when level goes below the set point plus the value
of the hysteresis.
o Low Alarms – Relay activates below set point. Relay will
deactivate when level goes above the set point plus the value
of the hysteresis.
High Alarm w/ Hysteresis
Low Alarm w/ Hysteresis
Note: Right click on any menu that you may have questions on to open the help menu.
Note: To reset, press the Clear Screen button.