Flowline LU84-5161 EchoSpan User Manual

Page 15

Advertising
background image

31 MAR 11

EchoSpan

15 of 22

Rev B

MN301550

How to set a Reverse the Current Output:

The default for EchoSpan is to have 4 mA at Empty and 20
mA at Full. This is the normal (NORM) setting. The output
can be reversed (REV) with 20 mA at Empty and 4 mA at
Full.

1. In MENU mode, select the TANK item.
2. When REV MA appears, press SELECT.
3. When REV appears, press SELECT.
4. When EXIT appears, press SELECT return to Top

Level Menu.


EchoSpan is now in the Reverse mode. To switch back to the
Normal mode, follow the instructions above and select
NORM under step 3.


How to set the SAFE setting:

The default for Fail-Safety (LOST) can be preset. The
choices are 4 mA, 20 mA, 21 mA, 22 mA and HOLD.

1. In MENU mode, select the SAFE item.
2. When the required setting appears, press SELECT.
3. When EXIT appears, press SELECT return to Top

Level Menu.


Advertising