INSTALLATION (cont.) 

Step Seven 

5. Stand Pipe:  A standpipe maybe used to dampen turbulence or separate surface foam from the point 

of measurement in the application.   

a. Pipe can be made of any material. 
b. Select a minimum 3” ID pipe for the stand pipe. 

i. A  2”  pipe  is  usable  with  the  LU77  series,  but 

this is the minimum size. 

ii. Pipe sizes larger than 3” can also be used. 

c. Use  a  coupling  and  reducer  bushing  to  attach  the 

EchoSwitch® to the pipe. 

i. With  the  LU77  series,  use  a  plastic  reducing 

bushing such as LM52‐1400 2” T x 1” T fitting or 
the LM52‐1410 2” S x 1” T fitting.  

d. The pipe length should run the measurement span and 

the bottom of the pipe should remain submerged at all 
times to prevent foam from entering the pipe. 

e. Cut  a  45°notch  at  the  bottom  of  the  pipe  and  drill  a 

1/4”pressure  equalization  hole  within  the  dead  band 
of the sensor.   

f. The  pumps  should  not  drive  liquid  past  the  open  end 

of the stand pipe which causes the liquid in the pipe to 
oscillate. 

 

 

 

EchoSwitch® 

LU77 

 

2” x 1”  

Reducer  

Bushing  

(TxT) 

 

2” Coupling  

(S x T) 

 

Vent Hole  

(1/4”) 

 

2” PVC  

Pipe 

 

 

LU77 attached to a LM52‐1400 

(2”x1” reducer bushing) and 2” 

Coupling (S x T). 

 

Avoid the use of a tee within the 

stand pipe.  A tee can create false 

signals that will negatively effect 

the sensor’s performance. 

 

 

 

 

 