Installation, Automatic fill, Automatic empty – Flowline LC52 DataPoint User Manual

Page 5: Relay input wiring, Low-level alarm, High level alarm, Vac power input wiring

Advertising
background image

Automatic Fill:

This system consists of a tank with a valve controller by the LC52. At

a low set point, the valve opens, filling the tank, At the high set point,

the valve closes. Part of a proper fail-safe design for this particular

system is that if power is lost to

the controller for any reason, the

valve filling the tank must close.

Therefore, we connect the valve

to the NO side of the relay. When

the relay is energized, the valve

will open and fill the tank. The

relay indicator will correspond

directly to the Open/Close status

of the valve.
NOTE: If the device’s load exceeds the rating of the controller’s

relay, a stepper relay of higher capacity must be used as part of the

system design.
Determining the settings of LATCH and INVERT
This is the way the system must operate:
• When the liquid level is below the low set point, the valve should

open, starting to fill the tank.

• When the liquid is above the low set point, the valve will remain

open.

• When the liquid reaches the high set point, the valve should

close.

Latch: In any two-sensor control system, LATCH must be ON.
Invert: Referring to the logic chart in Step One, we look for the set-

ting that will de-energize the relay (valve close) when both inputs are

ON (High level reached). In this system, Invert should be ON.

Automatic Empty:

In the same manner, the controller can be used to automatically empty

a tank with just a change to the setting of the INVERT switch.
• The valve is still connected to the NO side of the relay to allow

for a power failure fail-safe condition.

• The normal state of the valve is closed. In this state, we want the

relay to be energized at the high set point (opening valve to drain

tank). The relay will de-energize at the low set point (closing

valve).

Note: A fail-safe design is important. If the tank is being passively

filled, and a valve must be used to actively empty it, a power failure

to either the controller or the pump circuits will cause overflow.

Step Six

Step Seven

INSTALLATION

INSTALLATION

Relay Input Wiring:

The single pole, double throw isolated relay is

rated 250 VAC, 10 A, 1/2 Hp. The two terminals

marked Normally Open (NO) and Normally

Closed (NC) will be used in different applications.

Note: The “Normal” state is when the relay’s coil

is de-energized and the Red relay LED is Off.

Low-Level Alarm:

The goal is to make sure that the liquid level does not fall below a

certain point. If it does, an alarm is supposed to sound, alerting the

operator of a low-level condition.
If power is accidentally cut to the

controller, the sensor’s ability to

warn the operator of a low-level

condition could be lost. The sys-

tem must alert the operator not

only to low fluid level, but to con-

troller power loss.
To do this, connect the hot lead of

the alarm to the NC side of the

relay terminal of the LC52. If

power is lost, the relay will be de-energized, and the alarm will sound

(if there is still power to the alarm circuit itself). The alarm circuit

should have a non-interruptible power supply or some other indicator

or backup alarm to warn of a power failure in the alarm circuit.
In this application, the normal status of the sensor at the bottom of the

tank will be wet, and the relay will be energized holding the alarm

circuit open. Both the red relay LED and amber input LED will be on

simultaneously, so for this application, INVERT should be set to the

OFF position.

High Level Alarm:

In the same manner, the controller can be used to sound an alarm

when fluid reaches a high level, with just a change in the location of

the sensor and the setting of the INVERT switch.
• The alarm is still connected to the NC side of the relay to allow

for a power failure alarm.

• The sensor is normally dry. In this dry condition, we want the relay

to be energized so the alarm does not sound: i.e., the red relay LED

should be on whenever the amber sensor LED is off. So we turn

INVERT ON. If the fluid level rises to the high sensor point, the

sensor goes on, the relay de-energizes, and the alarm sounds.

VAC Power Input Wiring:

Observe the POWER SUPPLY label on the LC52.

The label identifies the power requirement (120 or

240 VAC) and the terminal wiring. Note: Polarity

does not matter with the AC input terminal.

POWER SUPPLY

120 VAC, 50 - 60 Hz
240 VAC, 50 - 60 Hz

L1

L2

GND

NO

NC

RELAY OUTPUT

250 VAC, 10A

C

RELAY 1

P O W E R

INVERT

DELAY

ON OFF

LATCH

Ground

Neutral

Hot

RELAY 1

P O W E R

INVERT

DELAY

ON OFF

LATCH

Ground

Neutral

Hot

RELAY 1

RELAY 2

P O W E R

INVERT

DELAY

INVERT

DELAY

ON OFF

LATCH

RELAY 1

RELAY 2

P O W E R

INVERT

DELAY

INVERT

DELAY

ON OFF

LATCH

Advertising