Application examples troubleshooting, Automatic fill, Automatic empty – Flowline LC40, LC41 and LC42 Remote Controller User Manual

Page 6: Controller logic, Relay latch logic table

Advertising
background image

Step Eight

Step Nine

APPLICATION EXAMPLES

TROUBLESHOOTING

Automatic Fill:

This system consists of a tank with a high level sensor, a low level
sensor, and a pump that is controlled by the controller. Part of a prop-
er fail-safe design for this particu-
lar system is that if power is lost to
the controller for any reason, the
pump filling the tank must be
turned off. Therefore, we connect
the pump to the NO side of the
relay. When the relay is energized,
the pump will turn on and fill the
tank. The relay indicator will cor-
respond directly to the On/Off sta-
tus of the pump.

NOTE: If the pump motor load exceeds the rating of the controller’s
relay, a stepper relay of higher capacity must be used as part of the
system design.

Determining the settings of LATCH and INVERT

This is the way the system must operate:

When both the high and low sensors are dry, the pump should turn
on, starting to fill the tank.

When the low sensor gets wet, the pump should stay on.

When the high sensor gets wet, the pump should turn off.

Latch:

In any two-sensor control system, LATCH must be ON.

Invert:

Referring to the logic chart in Step Nine, we look for the set-

ting that will de-energize the relay (start the pump) when both inputs
are wet (Amber LEDs). In this system, Invert should be ON.

Determining A or B input connections:

When LATCH is ON,

there is no effective difference between Input A and B, since both sen-
sors must have the same signal in order for status to change. When
wiring any two-input relay section, the only consideration for hook-
ing a particular sensor to A or B is if LATCH will be OFF.

Automatic Empty:

Note that a similar system logic can be used for an automatic empty
operation simply by controlling a pump that pumps fluid out of the
tank instead of into it. However, note the importance of fail-safe
design. If the tank is being passively filled, and a pump must be used
to actively empty it, a power failure to either the controller or the
pump circuits will cause overflow.

Alternatively, an electrically-controlled drain valve could be used. In
this case, the valve should be a type that will automatically open if
power is lost; in other words, power must be used to hold it closed.
The valve would be connected to the NO side of the relay—if power
is lost to the controller, the relay de-energizes, the valve loses the
power that was holding it shut, and fluid will drain from the tank into
some other safe containment until
power is restored. In this system,
whenever the red relay LED of the
controller is ON, the drain is
closed, allowing fluid to rise.

In this case, Invert should be On:
when both sensors are wet, the
relay de-energizes, the switch to
the valve opens, and the tank will
drain.

Controller Logic

For all controllers, please use the following guide to understand the
operation of the FLOWLINE LC40/LC41/LC42 controllers.

1. Make sure the Green power LED is On when power is supplied to

the controller.

2. The input LED's on the controllers will be Amber when the switch

is wet and Green when the switch is dry. Note: see Step 4 regard-
ing reed switches.
If the LED's are not switching the input LED,
test the level switch.

3. When the input LED's turn Off and On, the relay LED will also

switch. With invert Off, the relay LED will be On when the input
LED is On and Off when the input LED is Off. With invert On,
the relay LED will be Off when the input LED is On and On when
the input LED is Off.

4. LC41 and LC42 model only: When both inputs are wet (Amber

LED's On), the relay will be energized (Red LED On). After that,
if one switch becomes dry, the relay will remain energized. Only
when both switches are dry (both amber LED's Off) will the con-
troller de-energize the relay. The relay will not energize again
until both switches are wet. See the Relay Latch Logic Chart
below for further explanation.

Relay Latch Logic Table:

Relay 2 can either be a independent relay similar to relay 1 or can be
a latching relay with latch ON. With Latch Off, relay 2 will only
respond to the INPUT 2A setting. INPUT 2B will be ignored.

With Latch ON, relay 2 will actuate when INPUT 2A and INPUT 2B are
in the same condition. The relay will not change its condition until both
inputs reverse their state.

Caution:

Some sensors (particularly buoyancy sensors) may have

their own inverting capability (wired NO or NC). This will change the
logic of the invert switch. Check your system design.

R E L A Y 1

R E L A Y 2

P O W E R

- +

- +

I N V E R T

D E L A Y

I N V E R T

D E L A Y

R E L A Y 1

R E L A Y 2

P O W E R

- +

- +

I N V E R T

D E L A Y

I N V E R T

D E L A Y

Invert OFF

Latch OFF

INPUT 2A*

ON

OFF

INPUT 2B*

No Effect

No Effect

Relay

ON

OFF

Invert OFF

Latch ON

INPUT 2A*

ON

OFF

ON

OFF

INPUT 2B*

ON

ON

OFF

OFF

Relay

ON

No Change

No Change

OFF

Invert ON

Latch Off

INPUT 2A*

ON

OFF

INPUT 2B*

No Effect

No Effect

Relay

OFF

ON

Invert ON

Latch ON

INPUT 2A*

ON

OFF

ON

OFF

INPUT 2B*

ON

ON

OFF

OFF

Relay

OFF

No Change

No Change

ON

Advertising