4.2 application conditions

Ambient temperature: max. +55 °C
Permitted medium temperature and permitted media depending on
seal material:

Seal

material

Medium

temperature

Permitted media

FKM

0 ... +90 °C

Per-solutions, hot oils without additives,
diesel and heating oil without additives,
detergent solution

EPDM

-30 ... +90 °C

Oil and grease-free liquids, cold and
hot water

NBR

0 ... +80 °C

Cold and warm water, neutral gases

Operating duration: Unless otherwise indicated on the type label,

the solenoid system is suitable for continuous
operation

Important information for functional reliability during continuous
operation: If standstill for a long period at least 1-2 activations
per day are recommended.

Service life:

High switching frequency and high pressures

reduce the service life

4.3 conformity

In accordance with the EC Declaration of conformity, Type 0280 is com-
pliant with the EC Directives.

4.4 standards

The applied standards, which verify conformity with the EC Directives,
can be found on the EC-Type Examination Certificate and / or the EC
Declaration of Conformity.

4.5 Type label

Type

Operating

principle

Orifice

Seal material

Body material

Identification

number

Manufacturer code

Voltage, Frequency,

Power consumption

Connection thread, Operating

pressure

0280 A 8,0 NBR MS

Made in Germany

00041346

W17MG

220-230V 50-60 Hz 8W

G1/2 P

N 0.2

- 1

6 bar

english

6

5

insTallaTiOn

5.1 safety instructions

Danger!

Risk of injury from high pressure in the equipment!

▶ Before loosening the pipes and valves, turn off the pressure and

vent the lines.

Risk of injury due to electrical shock!

▶ Before reaching into the device or the equipment, switch off the

power supply and secure to prevent reactivation.

▶ Observe applicable accident prevention and safety regulations for

electrical equipment.

Warning!

Risk of injury from improper installation!

▶ Installation may be carried out by authorized technicians only and

with the appropriate tools.

Risk of injury from unintentional activation of the system and an

uncontrolled restart!

▶ Secure system from unintentional activation.

▶ Following assembly, ensure a controlled restart.

5.2 Before installation

Installation position: any, actuator preferably upwards.
Procedure:

Check pipelines for dirt and clean.

Install a dirt filter before the valve inlet (

≤ 400 µm).

5.3 installation

note!

Caution risk of breakage!
• Do not use the coil as a lever arm.

Hold the device with a open-end wrench on the body and screw
into the pipeline.

Valve body must not be installed under tension.
Sealing material must not get into the device.

Observe direction of flow:
The arrow on the body indicates the direction of flow (no function in
opposite flow direction).

english

7

5.4 electrical connection of the cable plug

Warning!

Risk of injury due to electrical shock!

▶ Before reaching into the system, switch off the power supply and

secure to prevent reactivation.

▶ Observe applicable accident prevention and safety regulations for

electrical equipment.

If the protective conductor is not connected, there is a risk of electric
shock!

▶ Always connect protective conductor and check electrical continuity.

Procedure:

Tighten cable plug (for permitted types see data sheet), observing
max. torque 1 Nm.

Check that seal is fitted correctly.

Connect protective conductor and check electrical continuity.

Authorized cable plug

e.g. Type 2508 or other suitable

cable plug in accordance with

DIN EN 175301-803 Form A

Seal

max. 1 Nm