11 replacement parts, 1 replacement part sets – Burkert Type 2012 User Manual

Page 18

Advertising
background image

18

Replacementparts

Type 2012

10

malfuncTiOns

malfunction

reason

remedial action

Actuator
does not
switch

Pilot air port
interchanged

→

Connect lower (CFA,
CFI) or upper (CFB,
CFI) control air
connection

Pilot pressure too low

→

Observe pressure
specifications on the
type label

Medium pressure too
high
Flow direction reversed

→

Observe direction
arrow on the body

Valve is not
sealed

Dirt between seal and
valve seat

→

Installing dirt trap

Seat seal worn

→

Installing new seat seal

Flow direction reversed

→

Observe direction
arrow on the type label

Medium pressure too
high

→

Observe pressure
specifications on the
type label

Pilot pressure too low

Valve is
leaking on
the release
bore

Packing gland worn

→

Renew packing gland
or replace actuator

Tab. 3: Malfunctions

11

replacemenT parTs

Caution!

risk of injury and/or damage by the use of incorrect parts!
Incorrect accessories and unsuitable replacement parts may cause
injuries and damage the device and the surrounding area.

▶ Use only original accessories and original replacement parts from

Bürkert.

11.1 replacement part sets

The following spare part sets are available for the globe control valve
Type 2012:
• Seal set packing gland,
• Valve set (seal material PTFE),
• Valve fittings (seal material PTFE),
• Seal set swivel plate.

11.1.1 seal set packing gland

Contain: packing gland and graphite seal

actuator size

nominal diameter

Order number

175

65

155 483

175, 225

80

155 484

175, 225

100

155 485

english

Advertising