Burkert Type 2031 User Manual

Page 8

Advertising
background image

8

Installation

Type 2031 INOX

devices with Vg/Vs welded body

Before welding the body, the actuator must be removed.

6.2 Installation

WarnIng!

risk of injury from incorrect installation!
Non-observance of the specified tightening torque is hazardous

as the device may be damaged.

▶ Observe tightening torque during installation.

6.2.1 Devices with VG/Vs welded body

Before welding the body, the actuator must be removed.

Remove actuator and diaphragm from the body
procedure for control function a:

→

Apply control air connection with compressed air (5.5 bar).

→

Loosen fastening screws in diagonal pairs and remove actuator
together with diaphragm from the body.

→

Weld body into the pipeline.

procedure for control function B:

→

Loosen fastening screws in diagonal pairs and remove actuator
together with diaphragm from the body.

→

Weld body into the pipeline.

6.2.2 Installation

installation for actuator with control function a:

→

Align diaphragm.
the mark tab of the diaphragm must be vertical to the flow
of direction.

→

Place actuator on the body.

→

Apply control air connection with compressed air (5.5 bar).

→

Lightly tighten fastening screws crosswise until the diaphragm is
situated between the body and actuator.
do not tighten screws yet!

→

Switch diaphragm valve twice.

→

Tighten fastening screws.

Observe tightening torque (2.5 Nm)!

installation for actuator with control function B:

→

Align diaphragm.
the mark tab of the diaphragm must be vertical to the flow
of direction.

→

Place actuator on the body.

→

Lightly tighten fastening screws crosswise until the diaphragm is
situated between the body and actuator.
do not tighten screws yet!

→

Apply control air connection with compressed air (5.5 bar).

→

Switch diaphragm valve twice.

→

Tighten fastening screws.

Observe tightening torque (2.5 Nm)!