Burkert Type 6014 User Manual

Page 4

Advertising
background image

8

6.

INSTALLATION

6.1. Safety instructions

DANGER!

Risk of injury from high pressure in the equipment/device.

▶ Before working on equipment or device, switch off the pressure and

deaerate/drain lines.

Risk of electric shock.

▶ Before working on equipment or device, switch off the power supply

and secure to prevent reactivation.

▶ Observe applicable accident prevention and safety regulations for

electrical equipment.

Risk of injury from improper installation.

▶ Installation may be carried out by authorized technicians only and

with the appropriate tools!

▶ Secure system from unintentional activation.

▶ Following installation, ensure a controlled restart.

6.2. Fluid installation

DANGER!

Risk of injury from high pressure in the equipment/device.

▶ Before working on equipment or device, switch off the pressure and

deaerate/drain lines.

Installation position: any, coil preferably upwards.

Procedure:

→

Before installation, clean any possible dirt off the pipelines and flange

connections.

→

If required, install a dirt trap to prevent malfunctions.

Mesh size:

0,2 – 0,4 mm

Pay attention to the flow direction of the valve.
from 1(P) → 2(A) (Circuit function C) or

from 1(P) → 2(B) (Circuit function D)

english

9

Valve with threaded connection:

→

Use PTFE tape as sealing material.

NOTE!

Caution risk of breakage.

▶ Do not use the coil as a lifting arm.

→

Hold the device with a suitable tool (open-

end wrench) on the body and screw into

the pipeline.

Valve with flanged connection:

→

Remove the cover plate.

→

Loosen the nut on the coil and remove coil.

Seal

Nut

Coil

Cover plate

Manifold

Fig. 2:

Valve with flanged connection

WARNING!

Risk of injury due to escaping medium.

▶ Make certain the seals included with delivery are properly seated in

the valve.

▶ Ensure that the manifold is even.

▶ Ensure that the surface quality of the manifold is adequate.

→

Insert the seal into the body.

→

Screw the body onto the manifold (tightening torque: max. 1.5 Nm).

→

Attach the coil and screw on the nut (tightening torque: max. 5 Nm).

english

10

6.3. Electrical connection with cable plug

DANGER!

Risk of electric shock.

▶ Before working on equipment or device, switch off the power supply

and secure to prevent reactivation.

▶ Observe applicable accident prevention and safety regulations for

electrical equipment.

If the protective conductor contact between the coil and body is

missing, there is danger of electrical shock.

▶ Always connect protective conductor.

▶ Check electrical continuity between coil and body.

Seal

max. 1 Nm

Type 2508

Fig. 3:

Electrical connection with cable plug

Note the voltage and current type as specified on the type label.

→

Check that seal is fitted correctly.

→

Connect and tighten the cable plug (tightening torque: max. 1 Nm).

The cable plug can be turned by 4 x 90°.

Control of pulse version

Correct polarity is essential to ensure that the device functions:

Note identification on the upper side of the coil.
Pulse duration at least 50 ms.

switch ON +

+ switch OFF

Terminal 1

Terminal 2

Protective conductor connection

Fig. 4:

Pulse version

english

Type 6014