Burkert Type 8605 User Manual
Page 23

23
Serial Communication
Example:
All data as hexadecimal numbers (prefix 0x) short frame
Primary master
Short address 0
data sent
data received
Set-point value settings digital 0.0% (
•
0x00000000 IEEE 754)
0xFF 0xFF 0x02 0x80 0x92 0x05 0x01 0x00 0x00 0x00 0x00 0x14
0xFF 0xFF 0x06 0x80 0x92 0x07 0x00 0x00 0x01 0x00 0x00 0x00 0x00 0x12
Set-point value settings digital 50.0% (
•
0x42480000 IEEE 754)
0xFF 0xFF 0x02 0x80 0x92 0x05 0x01 0x42 0x48 0x00 0x00 0x1E
0xFF 0xFF 0x06 0x80 0x92 0x07 0x00 0x00 0x01 0x42 0x48 0x00 0x00 0x18
Set-point value settings digital 100.0% (
•
0x42C80000 IEEE 754)
0xFF 0xFF 0x02 0x80 0x92 0x05 0x01 0x42 0xC8 0x00 0x00 0x9E
0xFF 0xFF 0x06 0x80 0x92 0x07 0x00 0x00 0x01 0x42 0xC8 0x00 0x00 0x98
Switch set-point value settings to analog set-point value settings:
•
0xFF 0xFF 0x02 0x80 0x92 0x05 0x00 0x00 0x00 0x00 0x00 0x15
0xFF 0xFF 0x06 0x80 0x92 0x07 0x00 0x00 0x00