Burkert Type 8631 User Manual
Page 6

Bus drive via DeviceNet
DIP 1
[2
0
=1]
DIP 2
[2
1
=2]
DIP 3
[2
2
=4]
DIP 4
[2
3
=8]
DIP 5
[2
4
=16]
DIP 6
[2
5
=32]
MAC ID
off
off
off
off
off
off
0
on
off
off
off
off
off
1
off
on
off
off
off
off
2
...
...
...
...
...
...
...
off
on
on
on
on
on
62
on
on
on
on
on
on
63
Bus drive via DeviceNet
pired
)
1 Bus
ow)
+
+
w)
Plug connector
for Initiator S1
Plug
connector
for valve
LED for initiator 1
LED for
valve 1
MNS LED =
Module Network Status
Power LED
Plug connector
for initiator S2
Connection
for bus and
supply
DIP switches for
address and data rate
LED for initiator 2
Bus connection (circular plug connector M 12, 5-pole)
Settings of the DeviceNet address
Setting the network data rate
Adaption to the data rate
of the network
MAC ID - Medium Access Control Identifier:
DIP1=off=0, DIP1=on=1
MAC ID=DIP 1*2
0
+DIP2*2
1
+...+DIP6*2
5
DIP 7
DIP 8
Network
data rate
off
off
125 kBaud
on
off
250 kBaud
off
on
500 kBaud
on
on
not allowed
BUS COMMUNICATION
BUS COMMUNICATION
BUS COMMUNICATION
Bus drive via DeviceNet