Field bus interface according to IEC 1158-2
Communication device following the FISCO model
Permissible operational voltage:
9 - 15 V
Maximum operating current:
< 33 mA
Maximum current in case of a fault:
< 53 mA
Max. permissible power of the supply unit:
1.93 W
Permissible temperature range:
- 25 to 50 °C
Insulation class:
3
Protection class of housing:
IP 65
Explosion protection to EN 50020 EEx ia IIC T6
3
GENERAL TECHNICAL DATA FOR THE I/O BOX TYPE
8642 WITH PROFIBUS-PA CIRCUIT
4
INSTALLATION AND COMMISSIONING
Î
Work on the device should only be carried out by specialist staff using the
correct tools!
Î
Always switch off the voltage supply before working on the system!
ATTENTION!
Never dismount piping or valves from systems which are
under pressure!
NOTE
The I/O Box Type 8642 fulfils the regulations of the EMC law:
Resistance to interference
EN 50082-2
Transmitted interference
EN 50081-2