Malfunctions

mAlfunCTions

10.

malfunction

possible cause

remedial action

Valves do not switch:

No or inadequate oper-
ating voltage.

Check the electrical connection.

→

Ensure the operating voltage according to type plate.

→

Inadequate or no
pressure supply.

Design the pressure supply with the largest possible

→

volume (even for upstream devices such as pressure
controllers, maintenance units, shut-off valves, etc.).
minimum operating pressure ≥ 2.5 bar

Valves switch with a
delay or blow off at the
deaeration connections:

Inadequate or no
pressure supply.

Design the pressure supply with the largest possible

→

volume (even for upstream devices such as pressure
controllers, maintenance units, shut-off valves, etc.).
minimum operating pressure ≥ 2.5 bar

Deaeration of the
exhaust air ducts inad-
equate due to too small
or dirty silencers (back
pressures).

Use appropriately sized silencers or expansion tanks.

→

Clean dirty silencers.

→

Impurities or foreign
objects in the pilot valve
or main valve.

Apply pulsed pressure to the exhaust air ducts to blow

→

out the impurities; install a new pilot valve or main
valve if this procedure is unsuccessful.