Pneumatic connection to actuator – Burkert Type 8694 User Manual

Page 11

Advertising
background image

11

Installation

4.5.

Pneumatic connection to
actuator

Using the hoses supplied in the accessory kit, make the pneu-
matic connection between the positioner and actuator with the
following "“Tab. 1: Pneumatic connection to actuator”".

NOTE!

Damage or malfunction due to ingress of dirt and moisture!
• To comply with protection class IP65 / IP67, connect the con-

trol air connection (for CF A und CF B) which is not required to

the free chamber of the actuator or seal with a plug.

Control air connection 2

1

Control air connection 2

2

upper chamber

lower chamber

Fig. 10: Pneumatic connection to actuator

Control function

Pneumatic connection
Type 869x to actuator
Control air
connection
Type 869x

Actuator input

A

Process valve
closed in rest
position
(by spring force)

2

1

lower chamber of the
actuator

2

2

Should be connected
to the upper chamber
of the actuator

B

Process valve open
in rest position
(by spring force)

2

1

upper chamber of the
actuator

2

2

Should be connected
to the lower chamber
of the actuator

I

Process valve
closed in rest
position

2

1

lower chamber of the
actuator

2

2

upper chamber of the
actuator

Process valve open
in rest position

2

1

upper chamber of the
actuator

2

2

lower chamber of the
actuator

Tab. 1: Pneumatic connection to actuator

english

Types 8692, 8693, 8694