Electrical installation, 2 electrical installation – Burkert Type 8695 User Manual
Page 31
Advertising

31
Electricalinstallation24VDC
9.2
electrical installation
configuration
circular plug (m12 x 1, 8-pole):
6
1
7
5
4
3
2
8
Figure 18:
Circular plug M12 x 1, 8-pole
pin
Wire color
2)
Designation
Configuration
external circuit / signal level
1
white
limit switch top
IN 1 (=Top)
1
2
GND
+ 24 V
IN 1
IN 2
{
100K
2
brown
limit switch bottom
IN 2 (=Bot)
3
green
Supply voltage
GND
3
4
GND
24 V
4
yellow
Supply voltage +
24 V DC
5
grey
Valve control unit +
Valve +
5
6
24 V
GND
6
pink
Valve control unit -
Valve -
7
-
not used
8
-
not used
Table 3:
Connection with circular plug-in connector
→
Connect the control head according to the table.
When the supply voltage is applied, the control head is operating.
→
).
2)
The indicated colors refer to the connecting cable available as an accessory (919061).
english
Type 8695
Advertising