INSTALLATION

1. Cut a 2” round hole in duct or plenum with a hole saw or

duct knife for insertion of the UV lamp.

2. Insert the lamp into the hole. Magnets on the mounting

plate will hold the UV lamp assembly secure – no screws
are necessary. If mounting on ductboard, secure unit

with tape, or cut a piece of sheet metal 4” x 4” and cut 2”
hole in middle. Tape sheet metal plate to ductboard

and insert lamp through holes.

3. Attach power supply in a suitable location and connect the

power supply to 24VAC power.

The MicrobeSwatter

®

SweetShot requires a 50 VA

Transformer to correctly power ultraviolet lamp air

purifier.

4. Connect lamp cable from power supply to lamp.
5. If mounting inside duct, order AGMGF magnetic mounting

bracket (accessory not included). Attach UV lamp assembly
to mounting bracket and attach bracket (with magnet on
backside) to any metal surface – no screws are necessary.

The MicrobeSwatter

®

SweetShot is designed for air

disinfection, deodorization and surface irradiation and installs
into the air handling system or ductwork. Select a mounting
location that offers sufficient space for the mounting plate
3” x 3” and enough internal space for the UV lamp – 16”. In
addition, allow for sufficient space for removal (pulling out) of
the 16.25” lamp assembly. Installation also requires access to
24 VAC electrical power.

• Do not install where UV lamp is visible

• Do not install in outdoor applications

• Do not expose wiring or plastic to UV light

• Do not install beneath a humidifier

• If installed near an air filter, check with the filter

manufacturer for UV properties & safety.

• The unit can be installed in either the return or

supply air side for for air stream disinfection

or mounted anywhere surface irradiation is needed.

Steps to replace ultraviolet lamps:

1.

READ THE WARNINGS ABOVE.

2. Make sure power is off to the HVAC system and the UV

lamp is off before opening any service panels.

3. Remove the rubberized cap covering the center part of the

lamp assembly inserted into the air duct.

4. Pull out the UV lamp assembly (the lamp assembly is held

in place with strong magnets), and insert new UV lamp

assembly.

5. Reattach the rubberized cap making sure the lamp socket is

pushed onto the metal pins tightly.

6. Restore power to the HVAC system.

SPEcIFIcATIONS

REPLAcING ThE LAMP

Dimensions:

• Mounting Plate: 3" x 3"
• UV Lamp 1.75" x 16.25"
• Duct Mounting Hole: 2"

Weight:

• UV Lamp Assembly: 6 oz

Electrical

• 24 VAC, 2 Amp
• UL Listed Electronic Ballast

UV Lamp

• 36 watt, 105 uw/cm² @ 1 mtr

Transformer NOT included
50 VA Required- GA3501 Recommended
AGMGF magnetic mounting bracket
(accessory not included)

WARNING

Electrical Shock

–The unit is to be wired into 24 VAC

electrical power.

Component Failure May Result

– Dedicated 50 VA

transformer required, not included.

Ultraviolet Light is Harmful

– Never look at a lit ultraviolet

lamp without UV protective glasses and skin coverings.
Unplug the lamp before servicing.

Ultraviolet Lamp May Cause Injury

– Ultraviolet lamps

are made of glass and therefore somewhat fragile. Safety
glasses and gloves should be worn when handling a UV
lamp. In addition, UV lamps can be very hot and cause skin
burns. Allow lamp to cool before handling.

IMPORTANT

This unit must be installed in compliance and

in accordance with all national, state, and local

electrical and mechanical codes. Failure to do

so will void all expressed or implied warranty

representations.

Installation Manual

General Filters, Inc. 43800 Grand River Ave., Novi, Michigan 48375 • Toll Free (866) 476-5101

Phone: (248) 476-5100 • Fax (248) 349-2366 • www.generalaire.com

Ultraviolet Air Purification System