MAJOR COMPONENTS

Description

The Electronic Air Cleaner is approximately 24 x 28 x

15 in (61 x 71 x 38 cm) with 6 in (15.2 cm) of the unit
above the ceiling. The cover and exhaust grill which
remain below the ceiling are hinged to allow access to the
cell and power board. The unit is rated at 700 CFM (1190
m

3

/hr) on the highest speed setting.

Cabinet

The cabinet is constructed of 20 gauge steel. The

external parts have a tough powder-coated, scratch-
resistant finish. Access to the collecting cell, power box
and prefilter is made by releasing the latches of the cover
and allowing it to swing down.

The cover is interlocked to cut power to the unit when

opened.

Prefilter

The washable prefilter measuring 12.5 x 20 in (31.75

x 50.8 cm) is constructed of multi-layers of aluminum
mesh for maximum filtration of large particles.

Collecting Cell

The dual voltage collecting cell is constructed of

heavy gauge aluminum to resist rust and damage. The
first stage, the ionizing section, is charged at

approximately 7500 VDC. The collecting plates are
alternately grounded and charged at 5000 VDC. The
arrow on the cells indicates the direction of air flow which
must point up towards the fan motor.

Motor and Fan Blade

The motor is 1/33 HP, 1050 RPM, 3-speed, controlled

by a 3-position slide switch. The motor is thermally
protected. The fan blade is 14 in (35.5 cm) with a 20

o

pitch.

Electrical Compartment

The removable power box contains the speed control,

system switch, high voltage power board, and
performance indicator light.

The interlock switch is located in the cabinet

body near the wiring compartment.

INSTALLATION

1. Read instructions carefully. Failure to do so may

result in product damage or injury.

2. Make sure the sizing is correct for your application.

3. Installation should be done by a knowledgeable

technician.

4. After installation, check out operation as provided in

these instructions.

Mounting

1. Remove the unit from the box and lay the unit on its

back, grill side up.

2. Release the grill by pushing the levers, located in the

exhaust grill, toward each other and lift up.

4.

Remove the ‘S’ hook from each chain, tilt cover up
until the cover releases from the back hinges.

5. Remove the cell and prefilter from the unit.

6. Holes are provided in the cabinet to accommodate

5/16 in (8 mm) threaded rod. Threaded rod can be
attached to the angle iron which is laid across the
joists, by drilling holes through these supports. Pass
threaded rod up through the supports and secure with
two nuts and washers. This will allow adjustment of

3

Fig. 2

— Coanda Air Flow

The

Air

Cleaner

creates a circular air
flow

pattern

which

never allows air to
rest at the ceiling.

Blower and motor are
hidden above ceiling tiles
for

space

conservation.

Advantageous

for

low

ceiling applications where
a larger unit would be
obstructive.


Hinged

cover

provides

convenient access to grill,
prefilter, collecting cell and
electrical

compartment.

Safety interlock cuts power
when cover is opened.

Rear hinges permit smooth
release of cover for easy
installation.


Removable intake grill for
easy cleaning.

Heavy duty collecting
cell captures airborne
pollutants and simply
washes clean.



Washable,

aluminum

mesh prefilter catches
lint and large particles
before

they

enter

collecting cell.



3-speed

fan

control

(not

shown)

allows

adjustment of air flow
to activity level in room.

Fig. 3

— Components

Advertising