GeneralAire SSCB-15 SERIES User Manual

Page 6

Advertising
background image

8. Return power to Air Cleaner. Test power board.

9. Replace power box cover panel and close cover.

Note: The power board has been set before shipping. It
is not usually necessary to reset the voltage to the new
load. If you do need to adjust the voltage refer to Setting
Voltage of Power Board section for more information.

Testing The 24 V Transformer

1. Remove the cover panel to the power box.

2. Disconnect the leads of the 24 V transformer from the

power board. See Fig. 5. Do not short the leads.

3. Push a screwdriver into the slot to defeat the interlock

switch and turn the Air Cleaner ON.

4. Measure the voltage across the leads with a

voltmeter. Voltage should read 25 - 28 VAC.

5. If no voltage is present, check the voltage from the

system switch.

6. If there is voltage to the transformer but no output,

replace the transformer.

Replacing The 24 V Transformer

Before

replacing

the

transformer,

check

the

resistance across the power board 24 V input terminals,
without the transformer connected. Resistance should
read above 20K ohms with an analog meter and above
4M ohms with a digital meter. If the resistance readings
are below these values, the power board may be the
cause of the transformer failure.

Before replacing the 24 V transformer, turn OFF the

power to the Air Cleaner at the source.

1. Remove the power box cover panel.

2. Disconnect the secondary leads from the transformer

to the 24 V terminals on the power board. See Fig. 5.

3. Remove the black primary lead from the system

switch. Remove the wire nut from the other primary
lead.

4. Remove the 2 hex head nuts and washers from the

transformer studs.

5. Remove the transformer.

6. Place new transformer over studs and re-install the

hex head nuts and washers to secure into place.

7. Connect the secondary leads (white) to the 24 V

terminals on the power board (P1 & P2).

8. Place one black lead on the system switch terminal.

9. Place the other black lead with the two white leads

from the terminal block and connect with the wire nut
you removed earlier.

10. Replace power box cover panel and close cover.

11. Turn ON the power to the Air Cleaner and test.

Setting Voltage Of Power Board

Voltage on the power board may drop below required

level when the installation area is too damp, too cold or

the input power to the unit is low. Voltage on power board
may be too high when the installation area is too dry or
too hot or the input power to the unit is high. By adjusting
the HV Adj. potentiometer, the voltage can be set to
optimum level. A high voltage meter capable of
measuring 10,000 VDC is required. To test and adjust
voltage level, perform the following procedure:

1. Turn the Air Cleaner OFF, with the cells in the unit.

2. Remove the power box cover panel.

3. Connect the ground of the high voltage meter to the

ground stud in the power box.

4. Turn the Air Cleaner ON and wait 5 minutes before

checking voltage to allow voltage on cells to stabilize.

5. Measure the voltage at HV1 and HV2 on the power

board.

6. Adjust the HV Adj. potentiometer until the voltage

reading matches the voltage in Fig. 5. Adjusting the
potentiometer clockwise decreases the voltage and
turning counter-clockwise increases the voltage.

7. Turn OFF the Air Cleaner.

8. Remove the high voltage meter.

9. Replace the power box cover panel and close cover.

10. Turn ON the Air Cleaner.

Setting Approximate Voltage Without High Voltage
Meter

A high voltage meter should be used to set the high

voltage. If one is not available, this method can be used.
This will only set an approximate voltage. After using this
method, the voltage should be reset with a high voltage
meter as soon as possible.

1. Remove power box cover panel, with the cells in the

unit.

2. Turn the HV Adj. potentiometer fully counter-

clockwise. The Air Cleaner may arc or snap at this
point.

3. Turn

the

HV

Adj.

potentiometer

clockwise

approximately a quarter turn.

4. Replace power box cover panel and close cover.

Testing for Voltage At The Cell

1. Remove the power box cover panel.

2. The cells must be in the Air Cleaner for this test.

3. Turn the Air Cleaner ON and defeat the safety

interlock switch.

4. Place a plastic handled screwdriver into the direction

arrow slot. Do not apply excessive force.

5. If there is a good snap then there is high voltage at

the cell.

Testing Cell For Bad Contacts

1. Remove the power box cover panel.

2. The cells must be in the Air Cleaner for this test.

3. Turn the Air Cleaner ON and defeat the safety

6

Advertising