Volt and 120-volt current sensing relays, Installation instructions, Model air cleaner installation – GeneralAire GA51 Current Sensing Relay User Manual

Page 2: Technical specifications, Checkout procedures, Volt and 120-volt current sensing relay

Advertising
background image

Model Air Cleaner Installation

Checkout Procedures

GA50

24-volt Model

GA51

120-volt Model

Voltage Range

21-24 VAC, 50-60 Hz

100-125 VAC, 50-60 Hz

Sensing Current

Minimum 5 amps

Minimum 5 amps

Operating Ambient Temperature Range

40˚F - 104˚F

40˚F - 104˚F

Dimensions

Load Ratings

Maximum (12 watts) 0.50 amps

Minimum (3 watts) 0.12 amps

Maximum (50 watts) 0.42 amps

Minimum (3 watts) 0.03 amps

Technical Specifications

24-volt and 120-volt Current Sensing Relay

24-volt and 120-volt Current Sensing Relays

Installation Instructions

AC

500

H.E

.P.A

Air

Cle

ane

r

AC500

H.E.P.A A

ir Cleane

r

H.E.P.A, th

e most eff

icient

air filtratio

n system

.

Replace H

.E.P.A.filte

r every two

years.

Replace pr

efilters eve

ry six mon

ths

for optimal

operation.

Call your h

eating con

tractor

for replace

ment filters

.

AC5

00

H.E.P

.A Air

Cleaner

H.E.P

.A, th

e mo

st eff

icien

t

air filt

ratio

n sy

stem

.

Repla

ce H.E

.P.A.fi

lter ev

ery tw

o yea

rs.

Repla

ce pre

filters

every

six m

onths

for opt

imal o

peratio

n.

Call y

our he

ating c

ontrac

tor

for rep

lacem

ent filt

ers.

EAC

2 x 4

Electrical

Box

120 VAC

120 VAC

GASI

EAC

1. Install the air cleaner according to the

manufacturer’s instructions.

2. Install the GA51 on the common wire of the blower

motor as shown in the diagram.

3. Open the main power junction box on the side of

the furnace and run the leads of the GA51 relay
into the junction box.

4. Connect the leads of the

GA51 relay in series with
one of the electronic air
cleaner leads. Connect the
remaining lead and ground
wire. The 120 VAC source
must be independent of
the furnace blower motor.

5. Check all wire connections, close junction box

and restore furnace to working order. Test proper
functioning by observing that the air cleaner’s
indicator lamp turns on when the blower runs and
turns off when the blower stops.

AC

500

H.E

.P.A

Air

Cle

ane

r

AC500

H.E.P.A A

ir Cleane

r

H.E.P.A, th

e most eff

icient

air filtratio

n system

.

Replace H

.E.P.A.filte

r every two

years.

Replace pr

efilters eve

ry six mon

ths

for optimal

operation.

Call your h

eating con

tractor

for replace

ment filters

.

AC5

00

H.E.P

.A Air

Cleaner

H.E.P

.A, th

e mo

st eff

icien

t

air filt

ratio

n sy

stem

.

Repla

ce H.E

.P.A.fi

lter ev

ery tw

o yea

rs.

Repla

ce pre

filters

every

six m

onths

for opt

imal o

peratio

n.

Call y

our he

ating c

ontrac

tor

for rep

lacem

ent filt

ers.

EAC

2 x 4

Electrical

Box

120 VAC

120 VAC

GASI

EAC

1. Replace all safety devices.

2. Reconnect power to furnace.

3. Activate furnace blower motor.

4. Check load for operation. It should now be working properly. Check

indicating lamp or other conditions showing that the load is receiving
power.

5. Switch off the blower unit. The power to the device should shut off.

6. If the device is activated properly and turns off when the power

through the common wire is removed, installation is complete.

7. If the device is not powered when the blower is turned on:

• Ensure the device’s power switch is in the “ON” position.

• Recheck all wiring.

• Check line fuses.

• Confirm that five or more amps is flowing through the control wire.

Wrap additional turns around the bracket if necessary.