II. INSTALLATION

1. A block valve of the globe/needle type should be

installed at the location of the pressure tapping.
Ball, butterfl y or gate valves are not rec om-
mend ed.

2. Recommended sensing tap pipe size is 1/2"

(DN15).

3. Location of pressure sensing tap should be in a

zone not subject to fl ow disturbances. Rec om-
mend a min i mum of 10 pipe diameters upstream
and 10 pipe diameters down stream from any
elbow, tee, valve, etc. that disturbs fl ow.

4. A pressure gauge is recommended at the location

of each tapping. Differential pressure designs
may in cor po rate a differential pressure gauge.

5. A pigtail siphon is required for hot condensing

fl uids, such as steam, to assure a liquid trap at
the controller. The siphon should be installed as
near to the pressure connection(s) on the control-
ler’s diaphragm hous ing as practical.

Figure 1: Recommended Piping Schematic for Pres sure

Reducing Control Valve with Positioner

I. DESCRIPTION AND SCOPE

The Model 764P is a pressure controller used for sensing static pressure, and outputting a pneumatic signal pro por -

tion al to the deviation from the setpoint.

The Model 764PD is a differential pressure controller used for sensing two static pressures (“HIGH” and “LOW”),

and outputting a pneumatic signal proportional to the deviation from the setpoint.

With proper materials selection, the units are suitable for gaseous, liquid or steam service. Refer to Tech ni cal Bulletin

764P-TB for design con di tions and selection rec om men da tions.

Use of oxygen gas as the IAS for a 764P or 764PD is outside the scope of this IOM, and is considered “special

construction”.

Abbreviations Utilized:

CCW – Counter Clockwise

P1 –

Inlet Pressure

P/P – Pneu mat ic-to-Pneu mat ic

CW – Clockwise

P2 –

Outlet Pressure

REV – Rev o lu tion or Re verse

DIR – Direct

PB –

Proportional Band

SIG – Sig nal

EXH – Exhaust

PC – Pressure Controller

SRV – Safe ty Relief Valve

IAS – Instrument Air Supply

PCV – Pres sure Control Valve

TR –

Con den sate Trap

PI

Pres

sure Indicator

V –

Vent

SECTION I

MODEL 764P & 764PD

PNEUMATIC PRESSURE CONTROLLERS

INSTALLATION, OPERATION & MAINTENANCE MANUAL (IOM)

IOM-764P / PD

12-13

TR

Supply

Supply @

P1

DIR

TR

Supply

Airset

SRV

PROCESS

Pigtail
Siphon

V