Caution a, Caution b, Iom-da2 2 – Cashco DA2 - Positive Differential User Manual

Page 2

Advertising
background image

IOM-DA2

2

PI

SRV

Outlet
@ P

2

Supply
@ P

1

(Shaded portion for steam/condensate systems)

Model 1000HP-1+6

Differential

Bypass

Blowdown-Drain

Blowdown-Drain

PI

10. Downstream Sensing Installation Considerations

– Internal or External Sensing:
a. The regulator may be installed with internal or

external sensing. Unless otherwise specifi ed,
the regulator is supplied by factory with internal
sensing. The regulator may be con vert ed in
the fi eld to external sensing (see Section VII
Maintenance, Paragraph H).

b. Reference DAG-TB, Table DAG-11 for rec-

ommendations for applying external pressure
sensing.

c. For internal sensing, no external line is re-

quired. For external sensing, use an external
control line. The line is connected from the port
(1/4" NPT) on the side of the body di a phragm
fl ange (see port 5 in Fig. 5) to a pressure tap.
The pressure tap should be located a minimum
of 10 pipe diameters downstream of the regu-
lator. It is recommended that the downstream
pressure tap be located close to the point of
use to minimize the adverse affect of variable
line losses. A tubing outer diameter of 0.25
inch is adequate for short sensing lines (less
than 4 feet). Use 3/8" tubing or 1/4" Sch 40
pipe for sensing lines of 5 to 50 feet.

d. For condensable vapors (i.e. steam) slope the

external sensing line downward 2 to 5 de grees
to outlet piping to prevent water pock ets, which
allows the diaphragm chamber to always be
self draining. The external sensing line may
be sloped upward for liquids or gases.

Recommended Piping Schematic for

Differential Pressure Reducing Station

CAUTION A

The proof test pressure must not exceed the
diaphragm and body rating for the regulator.

CAUTION B

Installation of adequate overpressure pro tec tion
is recommended to pro tect the reg u la tor from
over pres sure and all down stream equip ment
from dam age in the event of regulator failure.

Model DA2 & DA7 Differential
Pressure Reducing Regulator

A hydrostatic or pneumatic proof test is allowable un-
der the following conditions for the standard diaphragm
construction: Uniformly pressurize the valve body inlet,
valve body outlet, and loading chamber to the lesser
of the Diaphragm Proof Rating or 1.5 times the Outlet
Pressure Rating shown on the nameplate. For exam-
ple, a 1" DA2 with Cast Iron Body and Spring Chamber,
Neoprene Diaphragm (BC) has an Outlet Pressure Rat-
ing of 400 psig CWP. The lesser pressure of 1.5X 400
psig = 600 psig and the BC diaphragm proof rating of
1250 psig is 600 psig. Therefore, uniformly pressur-
izing the DA2 to 600 psig is allowable.

TABLE 1

MAXIMUM DIAPHRAGM RATING *

- psig (Barg)

*Maximum setting of pressure safety device – safety relief valve or rupture disc.
**Not available for CI/CI, BRZ/CI, BRZ/BRZ, BRZ/CS, BRZ/SST, CS/CI & SST/CI constructions.
NA = NOT AVAILABLE

DIAPHRAGM

MATERIAL

BODY SIZE 1/2" - 2" (DN15-50)

BODY SIZE 3" - 4" (DN80-100)

STD DIAPHRAGM

CONSTRUCTION

**OPT-81 FULL DIAPHRAGM

SUPPORT

STD DIAPHRAGM

CONSTRUCTION

P

2

MAX

P

2

MAX

P

2

MAX

BC, EPR

1250

(86.1)

1250

(86.1)

800

(55.1)

NBR

450

(31.0)

1250

(86.1)

300

(20.6)

FKM, FKM+TFE, FK

700

(48.2)

1250

(86.1)

550

(37.9)

3-ply (PTFE+FKM+PTFE)

125

(8.6)

125

(8.6)

125

(8.6)

METAL

Be-Cu

1500

(103)

NA

NA

NOTE: The below ratings may be further "derated" by limitations thru the Pressure Equipment Directive (97/23/EC-May '97).