Cashco BQ User Manual

Page 2

Advertising
background image

IOM-BQ

2

a. Recommended installation is with the spring cham ber

directed upwards.

b. No corrosive fl uid should be utilized for spring cham-

ber loading.

c. System operation should ensure that loading pres-

sure (P

LOAD

) not exceed inlet pressure (P

1

); in ter nal

diaphragm damage may occur if this op er a tion al

mode occurs.

11. Regulators are not to be direct buried underground.

For insulated piping systems, recommendation is to

not insulate regulator.

12. Spring Chamber Vent Tap - Option -25: Pipe spring

chamber vent opening to remote location. Orient so as

not to take on rainwater.

10a. Basic Regulator - (Refer to Figure 1): Regulator may

be rotated around the pipe axis 360°. Recommended

positions are with the spring chamber vertical upwards,

or horizontal. Orient such that the spring chamber vent

hole does not collect rainwater or debris.

10b. Cryogenic Regulator - Option -5 or -36 (Figure 2):

a. Recommended installation is with spring cham ber

hang ing directly below the body in a ver ti cal down-

wards orientation. Allow water to drain; i.e. melting

frost, rain water.

b. Recommend inert purge gas to spring cham ber

through vent hole and out drain hole.

10c. Differential Regulator - Option -1+6 (Refer to Figure 3).

7. Slowly open the outlet (downstream) block valve ob serv-

ing the inlet (upstream) pressure gauge. De ter mine if

the regulator is fl owing. If not, slowly rotate the regula-

tor adjusting screw counterclockwise (CCW) until fl ow

begins.

8. Continue to slowly open the outlet (downstream) block

valve until fully open.

9. Observing the inlet (upstream) pressure gauge, rotate

the adjusting screw clockwise (CW) slowly until the inlet

pressure begins to rise. Rotate CW until the desired

setpoint is reached.

10. Continue to slowly open the inlet (upstream) block valve.

If the inlet (upstream) pressure exceeds the desired

setpoint pressure, rotate the adjusting screw (CCW)

until the pressure decreases.

11. When fl ow is established steady enough that both the

outlet and inlet block valves are fully open, begin to

slowly close the bypass valve if installed.

12. Develop system fl ow to a level near its ex pect ed normal

rate, and reset the regulator setpoint by turning the

adjusting screw CW to increase inlet pressure, or CCW

to reduce inlet pressure.

13. Reduce system fl ow to a minimum level and observe

setpoint. Inlet pressure will rise from the setpoint of Step
9. (Ensure that this rise does not exceed the stated upper
limit of the range spring by greater than 50% i.e. 30-80
psig (2.07 - 5.52 Barg) range spring, at maximum fl ow
the inlet pressure should not exceed 1.5 x 80 (5.6 Barg)
or 120 psig (8.3 Barg). If it does, consult factory.)

14. Increase fl ow to maximum level if possible. Inlet (up-

stream or P

1

) pressure should rise. Readjust setpoint

as necessary at the normal fl ow rate.

IV. STARTUP

* NOTE:

Systems sequencing operations at startup, normal opera-

tion, failure mode(s), and shutdown must assure that the pressure

(P

Load

) on the spring chamber does not exceed the pressure regis-

tering on the wetted side of the diaphragm. Should this "pressure

reversal" occur, particularly to metal diaphragms, the diaphragm

may be permanently damaged and cause improper operation.

P

1

> P

Load

Pressure reversal is normally caused by the inlet pressure

to a regulator being interrupted (automatically or manually).

1. Ensure the proper range spring is indicated to be within

the regulator by inspection of the unit's name plate. Apply

setpoint pressures that are only within the stated range.

2. When stating direction of rotation of the adjustment screw,

the view is with respect to looking down towards the

adjusting screw or its normal location.

3. Start with the block valves closed. A bypass valve may be

used to maintain inlet pressure in the upstream system

without changing the following steps.

4. Remove closing cap, if installed. Relax the range spring

by turning the adjusting screw counterclockwise (CCW)

a minimum of three (3) full revolutions. This reduces the

inlet (upstream) pres sure setpoint.

5. If it is a “hot” piping system, and equipped with a by-

pass valve, slowly open the bypass valve to pre-heat

the system piping and to allow slow expansion of the

piping. Ensure proper steam trap operation if installed.

Closely monitor inlet (upstream) pressure, via gauge, to

ensure not over-pressurizing. NOTE: If no bypass valve

is installed, extra caution should be used in starting up

a cold system; i.e. do everything slowly.

6. Crack open the inlet (upstream) block valve.

III. PRINCIPLE OF OPERATION

1. Movement occurs as pressure variations register on

the diaphragm. The registering pressure is the inlet,

P

1

or upstream pressure. The range spring opposes

di a phragm movement. As inlet pressure drops, the range

spring pushes the diaphragm down, closing the port;

as inlet pressure increases, the di a phragm pushes up

and the port opens.

2. A

com

plete diaphragm failure will cause the outlet

process fl uid to mix with the loading fl uid.

SECTION III

SECTION IV

Advertising