12 w – Cleveland Motion Controls DIN Rail Amplifier MWI-13261 Ultra Series Isolated REV BA User Manual

Page 15

Advertising
background image

MAN-13261

R

EV

BA

DIN

R

AIL

A

MPLIFIER

,

MWI-13261

U

LTRA

2.12 W

IRING

Most start-up problems are the result of mis-wiring or failure to reference the detailed information in this manual.
While a convenient basic wiring diagram can be found printed on the side label of the amplifier case, the diagram is
intended only as a helpful guide when checking field wiring. Additional information details can be found in the
subsequent sections of this manual and should be referenced before actual installation begins.

2.12.1 W

IRING TERMINATION

Terminal(s)

Conductor Size

Insulation Strip Length

Torque

Notes

All

1.5mm

2

/16 AWG

0.75mm

2

/18 AWG

0.5mm

2

/20 AWG

7 mm ( 0.28” )
7 mm ( 0.28” )
7 mm ( 0.28” )

0.5 Nm / 4.4 lb.-in.
0.5 Nm / 4.4 lb.-in.
0.5 Nm / 4.4 lb.-in.

One wire this size per terminal
Up to two wires this size per terminal
Up to two wires this size per terminal

2.12.2 T

RANSDUCER

W

IRING

1
2

5

4

3

6
7
8

4

BRN

3
2
1

BLU

BLK

WHT

LEFT XDCR

2

3

6
5
4

8
7

WHT

BLU

BRN

BLK

RIGHT XDCR

1

3

1

4

2

C

T

C

T

C

T

T

C

Figure 5 - Full-bridge Transducer Wiring

The successful amplification of low level signals from strain gage transducers requires particular attention to wiring
practices to avoid signal degradation in the industrial environment. Degradation can result from AC noise pickup
and/or DC errors. Refer to the following guidelines to identify measures that may help retain signal quality:

Use Ultra Series shielded transducer cables to reduce pickup of noise through electrostatic coupling.

Route cables away from sources of electrical interference (motor wiring, contactors, etc).

Connect the shield drain wire at one end only to discourage shield currents.

Optimum high frequency grounding requires low inductance connections that are enhanced with short

conductors or planar ground conductors (wide ground braids).

Do not pre-tin the stranded wires inserted into the pluggable connector.

A stable connection relies on the springy nature of stranded conductors to ensure a low contact

resistance despite thermal cycling and airborne impurities.

Avoid temperature extremes or gradients where electrical connections are made between different

metals. Connections can cause thermocouple voltages to be generated, which then become
superimposed on transducer signals.

In severe cases, additional shielding may be required in the form of either external flexible braided

shields or running the field wiring wires inside metallic conduit.

P

AGE

15

OF

30

Advertising