Voltage output default values – Impulse MAQ20-940 Configuration User Manual
Page 17

MAQ
®
20
Configuration Software Tool User Manual
11
Preset data can be output to between 1 and n sequential channels up to a maximum of 8 channels. Use
the Channels numeric up/down box in the Buffer Interval n Chans group box to enter the number of
channels to write to, and press the Set button to send the selection to the module. Data will remain in
module memory until the next power cycle. Press the Save button to store the settings in the module
nonvolatile memory. A Channels value of n specifies that preset data will be written to channels 0
through n-1. The default Channels setting is 8. The interval in milliseconds between written samples is
modified using the next numeric up/down box below the Channels box. The current setting is displayed
next to the box. Minimum interval is 10ms and the default value is 10ms. Press the Set button to send
the selection to the module and the Save button to store the settings in the module nonvolatile memory.
6.3
Voltage Output Default Values:
Default values for the module outputs upon power cycle, brown out, reset, or system fault can be
specified on a channel-by-channel basis. To change the default value, select a channel using the Chan #
numeric up/down box and enter the new value in the numeric up/down box. Press the Set button to send
the selection to the module and the Save button to store the settings in the module nonvolatile memory.