LAUREL

ELECTRONICS INC.

, 3183-G Airway Ave., Costa Mesa, CA 92626, USA • Tel 714-434-6131 • www.laurels.com 1

LAUREL

ELECTRONICS, INC.

Ethernet & 4-20 mA Output Transmitter

for Process Signals

Features

Ethernet Serial Data I/O, Modbus TCP or Laurel ASCII protocol

4-20 mA or 0-10V transmitter output, 16 bits, jumper selectable, isolated

Dual 120 mA solid state relays for alarm or control, isolated

5V, 10V or 24V dc transducer excitation output, isolated

200 mV, 2V, 20V, 200V, 300V & 600V DC voltage input ranges

2, 20, 200 mA and 5A DC current input ranges

All ranges factory calibrated

Digital span adjust from 0 to ±99,999, zero adjust from -99,999 to +99,999

Analog output resolution 0.0015% of span (16 bits), accuracy ±0.02% of span

Universal 85-264 Vac / 90-300 Vdc or 10-48 Vdc / 12-32 Vac power

Power over Ethernet (PoE) jumper selectable with 10-48 Vdc supply

Description

The Laureate process signal input transmitter provides six DC
voltage input ranges and four DC current input ranges for use
with a wide range of transducers whose output requires zero and
span adjustment. All ranges are factory calibrated and jumper
selectable. The two most sensitive voltage ranges, 200 mV and
2V, provide a high input impedance of 1 GΩ to minimize the load
on the voltage signal.

Fast read rate at up to 50 or 60 conversions per second while
integrating the signal over a full power line cycle is provided by
Concurrent Slope (Pat 5,262,780) analog-to-digital conversion.
High read rate is ideal for peak or valley capture and for real-time
computer interface and control. Digital signal filtering modes are
selectable for stable readings in electrically noisy environments.
The internal digital readings and analog output can be individu-
ally selected to be either unfiltered or filtered.

Digital signal filtering modes are selectable for stable readings
in electrically noisy environments. The internal digital readings
and analog output can be individually selected to be either
unfiltered or filtered.

An unfiltered selection updates after each conversion for
fastest response, up to 60/sec, while integrating the input
signal over a full power cycle. Fast read rate provides true
peak and valley readings and aids in control applications.

A batch average filter selection averages each 16
conversions for an update every 1/4 sec.

An adaptive moving average filter selection provides a
choice of 8 time constants from 80 ms to 9.6 s. When a
significant change in signal level occurs, the filter adapts by
briefly switching to the shortest time to follow the change, then
reverts back to its selected time constant. Another choice is
Auto, which provides an automatic time constant selection
based on the signal noise characteristics.

Standard features of Laureate LTE transmitters include:

Ethernet I/O, isolated. Supported protocols are Modbus
RTU and ASCII (tunneled via Modbus TCP) and Laurel ASCII.
The latter is simpler than the Modbus protocol and is recom-
mended when all devices are Laureates. Note that RS232 or
RS485 data I/O in lieu of Ethernet is provided by our LT Series
transmitters.

4-20 mA, 0-20 mA or 0-10V analog transmitter output,
isolated, jumper-selectable and user scalable. All selections
provide 16-bit (0.0015%) resolution of output span and 0.02%
output accuracy of a reading from -99,999 to +99,999 counts
that is also transmitted digitally. Output isolation from signal
and power grounds eliminates potential ground loop problems.
The supply can drive 20 mA into a 500 ohm (or lower) load for
10V compliance, or 10V into a 5K ohm (or higher) load for
2 mA compliance.

Dual solid state relays, isolated. Available for local alarm
or control. Rated 120 mA at 130 Vac or 180 Vdc.

Universal 85-264 Vac power. Low-voltage 10-48 Vdc or
12-32 Vac power is optional.

Discovery and configuration of Laureate Ethernet Nodes is
easily achieved with Laurel's Node Manager Software, and the
discovered transmitters can then be programmed using Laurel's
Instrument Setup Software. Both softwares run on a PC under
MS Windows and can be downloaded at no charge.

Advertising