American Water Heater 316888-004 User Manual
Page 17
www.americanwaterheater.com 17
FIGURE 11
B. ALL AIR FROM OUTDOORS: (See Figures 12, 13 and
14)
The confi ned space should be provided with two permanent 
openings, one commencing within 12 in. (30cm) of the top 
and one commencing within 12 in. (30cm) from the bottom 
of the enclosure. The openings should communicate 
directly, or by ducts, with the outdoors or spaces (crawl or 
attic) that freely communicate with the outdoors.
1. When directly communicating with the outdoors, each
opening should have a minimum free area of 1 square 
inch per 4,000 Btu per hour (5.5 cm
2
/kW) of total input
rating of all equipment in the enclosure (see Figure 
12).
FIGURE 12
2. When communicating with the outdoors through vertical
ducts, each opening should have a minimum free area 
of 1 square inch per 4,000 Btu per hour (5.5 cm
2
/kW)
of total input rating of all equipment in the enclosure 
(see Figure 13).
3. When communicating with the outdoors through
horizontal ducts, each opening should have a minimum 
free area of 1 square inch per 2,000 Btu per hour (11 
cm
2
/kW)) of total input rating of all equipment in the
enclosure (see Figure 14).
FIGURE 13
4. When ducts are used, they should be of the same
cross-sectional area as the free area of the openings to 
which they connect. The minimum short side dimension 
of rectangular air ducts should not be less than 3 in. 
(7.6cm) (see Figure 14).
FIGURE 14
5. Alternatively a single permanent opening may be used
when communicating directly with the outdoors, or with 
spaces that freely communicate with the outdoors. The 
opening should have a minimum free area of 1 square 
inch per 3,000 BTU per hour (8.3 cm
2
/kW) of total input
rating of all equipment in enclosure (see Figure 15).
FIGURE 15