Magnum Venus Plastech Mini Resin Meter User Manual
Page 6

PROBLEMS POSSIBLE CAUSE
REMEDIES
CANNOT ENTER INTO
1. Front panel disabled.
1. Check "Front Panel Accessible Functions With Program
PROGRAMMING Disable" section of the manual.
PROCESS, BATCH, OR
1. User input not properly programmed.
1. Verify programming of User Input parameters
TOTAL VALUES WILL NOT 2. User input Snk/Sre jumper configured improperly. 2. Configure Snk/Src jumper.
RESET WHEN A MANUAL
RESET IS PERFORMED
PRESCALER, PRESETS, OR 1. Front panel disabled.
1. Verify programming of Access parameters.
OUTPUT TIME VALUES CAN 2. Check "Front Panel Accessible Functions With Program
BE VIEWED BUT NOT Disable" section of manual.
CHANGED
UNIT COUNTS WHILE 1. User input reset mode set for momentary reset. 1. Program User input to a maintained reset.
RESET IS ACTIVATED
OUTPUT WILL NOT RESET
1. User input not properly programmed. 1. Verify programming of the user input parameters
OUTPUTS NOT WORKING 1. Output board not installed.
1. Install output board.
2. Improperly wired.
2. Check wiring.
3. Incorrect output board.
3. Check output board.
4. Defective output board.
4. Check or replace output board.