Actual subcool testing – Mastercool 52251 A_C SYSTEM ANALYZER User Manual

Page 4

Advertising
background image

4

www.mastercool.com

• Press

F2 (NEXT).

• Insert plug for clamp-on thermocouple into type K

thermocouple socket.
• Follow screen instructions to place clamp-on thermocouple.
• When temperature has stabilized, press

ENTER.

• Press

F2 (NEXT).

• Actual Superheat will be displayed.
• If Target Superheat test has been done, press

F1 (ANLY)

for analysis.
To use Pressure Transducer to Calculate Superheat
• Use ▲ or ▼ buttons to highlight Calculate.
• Press

ENTER.

• Use ▲ or ▼ buttons to select refrigerant.
• Press

ENTER.

• Insert plug from pressure transducer into pressure

transducer socket.
• Follow screen instructions to connect pressure transducer

to system.
• When saturated temperature stabilizes, press

F2 (NEXT).

• Insert plug from clamp-on thermocouple into type K

thermocouple socket.
• Follow screen instructions to place clamp-on thermocouple.
• When temperature has stabilized, press

ENTER.

• Press

F2 (NEXT).

• Actual Superheat will be displayed.
• If Target Superheat test has been done, press

F1 (ANLY)

for analysis.

ACTUAL SUBCOOL TESTING

• Use ▲ or ▼ buttons to highlight Actual Subcool.

• Press ENTER.
To Input Pressure Manually
• Use ▲ or ▼ buttons and highlight Input Manually.
• Press

ENTER.

• Use ▲ or ▼ Buttons to select refrigerant.
• Press

ENTER.

• Use ► and ◄, buttons to highlight unit and ▲ and ▼

buttons to adjust unit value to input high-side saturated

pressure.
• Press

ENTER.

• Saturated vapor temperature will be displayed.
• Press

F2 (NEXT).

• Insert plug for clamp-on thermocouple into type K

thermocouple socket.
• Follow screen instructions to place clamp-on thermocouple.
• When temperature has stabilized, press

ENTER.

• Press

F2 (NEXT).

• Actual Subcool will be displayed.
To use Pressure Transducer to Calculate Subcool

• Use ▲ or ▼ button to highlight Calculate.
• Press

ENTER.

• Use ▲ or ▼ button to select refrigerant.
• Press

ENTER.

• Insert plug from pressure transducer into pressure

transducer socket.
• Follow screen instructions to connect pressure transducer

Advertising