1600EP Series Instruction Manual Addendum

UPS Specifi cations

STANDARD MODELS: 3.6 kVA-C1; 3.6 kVA; 6 kVA; 8 kVA

Unit (Capacity)

3.6 kVA-C1

(3.1 kW)

1

3.6 kVA (3.1 kW)

1

6 kVA (5.1 kW)

1

8 kVA (6.8 kW)

1

General

Topology

True On-line

Certifi cations

UL, CUL, ISO 9001, NEMA/PE1-1993

Input Characteristics

Input Voltage

Single-phase, 208/240 Vac, -30% – +10%

Input Frequency

45 – 65 Hz (auto-sensing)

Input Capacity

3.6 kVA

6.0 kVA

8.0 kVA

Input Power Factor

> 0.95 for all loads

Current THD (linear load)

< 5% total harmonic distortion

Included AC Input Breaker
Rating

30 A/277 V

50 A/277 V

60 A/277 V

Battery Characteristics

Battery Type

Valve Regulated Lead Acid, Flame Retardant

Backup time, fully charged
@ 0.7 power factor, 77 °F

8 min.

minimum

2

14 min.

minimum

2

7 min.

minimum

2

Backup time, fully charged
@ 0.85 power factor, 77 °F

7 min.

minimum

2

10 min.

minimum

2

7 min.

minimum

2

Recharge Time

24 hr. (full), 12 hr. (90%) for internal batteries only

3

Battery Voltage (Nominal)

144 Vdc

216 Vdc

216 Vdc

288 Vdc

Output Characteristics

Output Voltage

Single-phase, 240/208/120 V

Output Voltage Regulation

± 3%

Output Frequency

±0.5 Hz/1 Hz/1.5 Hz (factory or authorized service center selectable only)

AUTO/MAN Frequency

Factory or authorized service center selectable only

Voltage THD

< 3% for linear load; < 6% for non-linear load

Common-Mode Noise

< 0.5Vrms

Rated Load Power Factor

0.85 (0.6 – 1.0) lagging

Effi ciency (ac-dc-ac)

> than 83% (without battery charge)

Voltage Transient

< ±8% (Load of 0 – 100 %)

Rated Output Current (rms)

15 A

25 A

33.3 A

Max. Peak Output Current

45 A

75 A

100 A

Inverter Overload Capacity

125% for 30 sec./150% for 10 sec.

Bypass Overload Capacity

125% for 10 min./1000% for 1 cycle