Gamatronic Electronic Industries Ltd.
34
POWER+ RM100,
3
X
208
V, User Guide, Release 2.7ys
Ac input
Ac input bypass
50 kVA
Load
175 A
Ac input
Ac input bypass
60 kVA
Load
225 A
Ac input
Ac input bypass
70 kVA
Load
250 A
Ac input
Ac input bypass
80 kVA
Load
300 A
Ac input
Ac input bypass
90 kVA
Load
350 A
Ac input
Ac input bypass
100 kVA
Load
500 kcmils,
600 V,
75 °C copper wire
350 A
* The recommended wire size is based on a 100 kVA system. The required circuit breaker size is
based on the actual maximum power of the system in kVA.
5.4.2
Dc wiring
To connect the battery cabinet to the UPS, use wire size of 300 kcmils, rated for 600 V,
75 °C copper wire.