Applications, Technical specifi cations – MaxPower Corp FirstLine 924 20, 30kW User Manual

Page 2

Advertising
background image

Applications

■

Public Buildings

■

Commercial and

Industrial

Facilities

■

Infrastructure Systems

■

High Security Areas

■

Schools, Universities

■

Single Point of Power

Protection

In the event of an AC power failure, FirstLine

®

924

automatically supports the connected lighting loads on
battery power and will continue to provide power without
any interruption for a full 90 minutes. When the utility power
returns to normal, FirstLine

®

924 will automatically recharge

the batteries to be ready for the next power disturbance.

Technical Specifi cations

Three-Phase Central Inverter for
Emergency Lighting Applications

General

■

On-line double-conversion topology

■

True sine wave output

■

Continuous, no-break operation

■

Three-phase system will support single

or three-phase loads

■

LCD front panel monitoring and control

■

Automatic system bypass

■

Circuit breaker protection integral with

battery cabinet, molded-case type

Input

■

Input Voltage Rating: 208Y/120 and

480Y/277 standard, Delta connection

with optional isolation transformer

■

Input Voltage Range:

+

/

-

10% system

start-up;

+10% /-20% from nominal

■

Input frequency: 60Hz

+

/

-

5%

■

Full load walk-in from 25% to 100% of

rated load in <5 seconds

■

Harmonic current distortion <5% at full load

■

Surge Withstand: Meets IEEE C62.41

Output

■

IGBT: true sine wave PWM inverter

■

Inverter output distortion: <5% THD

(100%

non-linear)

■

Inverter output distortion: <2% THD

(linear

loads)

■

Voltage regulation:

+

/

-

1% of nominal

at full load

■

Frequency: 60 Hz

Battery

■

Designed for easy maintenance

■

Standard backup time of 90 minutes at

full

load

■

Valve-Regulated Lead-Acid (VRLA) battery

■

10 year design life at 77°F (25°C)

Housing

■

Freestanding, NEMA 1 steel enclosure

■

Service access—top, front, all (4) sides

■

Bottom access for conduit entries

Environmental

■

Agency Compliance: UL924, FCC and

CSPR22, Class A

■

Operating temperature range 18°F (-8°C)

to 104°F (40°C)

■

Acoustical Noise: 75 db at 3 feet

■

Relative Humidity: 0-95% non-condensing

■

Meets NFPA 101 Life Safety, and

NEC

codes

■

Seismic Zone 4 certifi ed

Monitoring/Communications

■

Front Panel LCD Display

●

4 x 16 character display

●

System status and alarms

■

Communications Port

●

RS-232

●

Dry Contact (AS/400)

●

Remote monitoring

●

SNMP available option

In addition to meeting

life safety requirements,

the FirstLine

®

924 can

also increase the life

expectancy of the

protected lighting system

and reduce long-term

cost of ownership.

Your tailored power solutions provider