53MT6000 INSTRUCTION MANUAL

Database Editor 51

Scan Index:

This selection determines the execution rate of the control
program. This is an index number representing increments of 50
milliseconds (i.e., a value of 2 is an execution rate of 100
milliseconds, a value of 5 is an execution rate of 250
milliseconds). This value can be adjusted to suit program
requirements by entering a new value and clicking SAVE.

Scan File
Overrun Counter:

Incremented every time execution of the control algorithm takes
longer than the selected control scan time (determined by the
control scan index). This is an indication that the control program
is taking longer to execute than expected. This is not a fatal
indication and does not indicate a program failure. The program
is usually too long to execute in the expected time frame. Time
sensitive portions of the program may be affected by longer
execution times. This value may be reset to zero at any time.

Display Program: This number represents the index number of the display program

currently shown on the faceplate. Entering the desired display
index number and clicking SAVE can change the active display.

Background
Scan Index:

This selection determines the execution rate of the display
programs. This is an index number representing increments of 50
milliseconds (i.e., a value of 2 is an execution rate of 100
milliseconds, a value of 5 is an execution rate of 250
milliseconds).

Background
Overrun Counter:

Incremented every time execution of the control algorithm takes
longer than the selected control scan time (determined by the
control scan index).

Background
Program:

Setting the Background Program to "1" initiates the Easy Tune
algorithm. Refer to

Section 7.4.7.5

, Tuning Configurable

Parameters Wizard.

Display
Brightness Index:

Clicking on the "down arrow" reveals a list of 8 selections that
enable the brightness of the 53MC5000 display to be adjusted.
Selections range from * (DIM) to ******** (BRIGHT).

Seconds

:

Run Time Counter or Real Time Clock (53MC5000B only). This
value in conjunction with minutes, hours, days, months and years
is used to determine the amount of time the controller has been
actively running. In design level B version of the 53MC5000
controller, these values can also be used as a Real Time Clock.

Minutes:

Run Time Counter or Real Time Clock (53MC5000B only). This
value in conjunction with seconds, hours, days, months and years
is used to determine the amount of time the controller has been
actively running. In design level B version of the 53MC5000
controller, these values can also be used as a Real Time Clock.

Hours:

Run Time Counter or Real Time Clock (53MC5000B only). This
value in conjunction with seconds, minutes, days, months and
years is used to determine the amount of time the controller has
been actively running. In design level B version of the 53MC5000
controller, these values can also be used as a Real Time Clock.