Table 8 general specifications, Table 9 fault code/ audible alarm – PROLiNK IPS5000 User Manual
Page 17

- 15 -
Table 8 General Specifications
Safety Certification
CE(EN60950)
EMI Classification
EN62040-2, CLASS A
Operating Temperature Range
0°C to 45°C
Storage temperature
-15°C ~ 60°C
Altitude, operational
Elevation: 0 ~ 1500 Meters
Relative humidity
5% to 95% non-condensing
Audible Noise
60dB max
Cooling
Forced air, variable speed fan
Dimension
350mm(W)*110mm(H)*407mm(D)
Net Weight
9KG
Table 9 Fault code/ Audible alarm
Restart
Fault
Code
Protect
Function
Active
Mode
Condition
Warning
(O/P=ON)
Fault
(O/P=OFF) Operate Condition
--
Low DC
Voltage
Alarm
Inverter
DC voltage<Low
DC Alarm
1beep/2s -- --
--
0
Low DC
Voltage
Protection
Inverter
DC
Voltage<Low
DC Shut-down
--
Beep
continuous
Auto
Mains is normal
1
Over
Charge
Protection
Line
DC
Voltage>High
DC input
Shut-down
Beep
continuous
-- Manual
--
1
Over
Voltage
Protection
Standby
DC
Voltage>High
DC input
Shut-down
--
Beep
continuous
Auto
DC
Voltage<High
DC input
Shut-down
Recovery
110%~150%
load
1beep/0.5s,and
continuous 10s
Beep
continuous
Manual --
2
Over Load
Protection
Line/
Inverter
>150% load
1beep/0.5s,and
continuous 5s
Beep
continuous
Manual --
3
Output
Short Circuit
Protection
Inverter
Output
Voltage<20Vrms
--
Beep
continuous
Manual --
4
Fan Fault
Protection
Line/
Inverter
Fan Locked
Fan Defected
2beep/2s,and
continuous
1min
Beep
continuous
Manual --
5
Over Temp
Protection
Line/
Inverter
HEAT SINK
Temp≥100℃
--
Beep
continuous
Auto
HEAT SINK
Temp≤ 55℃
6
Back-EMF
Protection
Standby
Reverse input
and output
--
Beep
continuous
Manual --
9
Output
Abnormal
Inverter
(Output Voltage
<170Vrms and
output current
under 32Arms)
or Output
Voltage
>280Vrms
--
Beep
continuous
Manual --