OPERATION

PHW-IOM-2013-0214

SECTION 3

3-18

Single Boiler Outdoor Reset Programming

1. From the status summary screen press Confi gure. Press CH- Central

Heat Confi guration. See Figure 45.

FIGURE 45 - ACCESSING CENTRAL HEAT CONFIGURATION

2. Arrow over to Setpoint and verify that the Setpoint is the desired

temperature in relation to the Minimum outdoor temperature (see
Figures 46 and 47).

3. Arrow over to the Central Heat page (Figure 47). In this screen 3 of your

4 points that can be chosen for your outdoor reset curve. Maximum
outdoor temperature which relates to your Low water temperature
and your Minimum outdoor temperature relates to your Central
Heat Setpoint in the setpoint screen. Your Minimum boiler water
temperature should be the lowest temperature at which you want the
boiler to operate.

!