Operating Instructions

70400101

14

© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT

System Tests
The following system tests are performed during

normal operation. System tests are performed at a

minimum of every 24 hours.

Low Voltage Detection
If the voltage between terminals TH and GND on the

control is below 18.75VAC +/- 0.75VAC for more than

3 seconds the ignition control will turn off the gas

valve and will not attempt to spark. The Diagnostic

LED will display Error Code 5. The ignition control

will not enter Lockout Mode if a low voltage condition

is detected, but will enter Standby Mode and wait for

the low voltage condition to be cleared.
If the voltage between terminals TH and GND on the

control rises above 19.75VAC +/- 0.1VAC for at least

3 seconds, the ignition control will then enter Start Up

Mode.
Low Voltage Detection test is disabled during Run

Mode.

Gas Valve

The ignition control verifies that the gas valve is

connected. Failure of this test results in the ignition

control entering Lockout Mode with the Diagnostic

LED displaying Error Code 2.

Flame Probe Tests

Unexpected Presence of Flame

The Unexpected Presence of Flame test is performed

when no flame is expected. Failure of this test results

in the ignition control entering Lockout Mode with the

Diagnostic LED displaying Error Code 3.

Flame Monitoring

During the Flame Monitoring test, the flame is

checked to ensure the gas is being burned when the gas

valve is on. Failure of this test will result in the

ignition control entering Lockout Mode with the

Diagnostic LED displaying Error Code 3.

Diagnostic LED (DGN LED)

/ Error Codes

The Diagnostic LED or DGN LED is located by the

power connector on the ignition control. Refer to
Figure 5

. The Diagnostic LED will indicate the status

of the ignition control. Refer to Table 1.

The Diagnostic LED will flash error codes one half

second on and one half second off. Error codes are

separated by a one second pause before the code is

repeated.

LED Color

Description

Orange-Yellow

Initialization

Green

Standby / Normal Operation

Red

Fault Indication Code

Table 1

Error

Code

DGN LED status

Fault Type

1

Red

Ignition Control Internal Failure

2

2 Red Flashes

Gas Valve Not Connected

3

3 Red Flashes

Ignition/Flame Sense Failure

4

4 Red Flashes

Reset Switch is Shorted

5

Slow Red and Green Flashes

Low Voltage Detection

6

Fast Red and Orange Flashes

Ignition Control is in Reset Delay

TMB2176N

1

Diagnostic (DGN) LED

Figure 5

1