Configuring the daily tariff schedule – E-Mon E-PS-A-RTU-N User Manual

Page 77

Advertising
background image

Chapter 4 Power

S O F T W A R E

C O N F I G U R I N G S U M M A R Y E N E R G Y

A N D T O U R E G I S T E R S

PowerSmart+ Advanced Power Quality Meter

77

Parameter

Options

Default

Description

Summary/TOU Registers

Use Profl

Unchecked

Checked

Unchecked

Enables automatic daily profiling for
energy usage registers (both total and
tariff registers if TOU is enabled)

Dmd Profl

Unchecked

Checked

Unchecked

Enables automatic daily profiling for
maximum demand registers (both total
and tariff registers if TOU is enabled)

Sum Profl

Unchecked

Checked

Unchecked

Enables daily profiling for summary
registers (total of all tariffs)

Units

kWh, kvarh, kVAh,

m3, CF (cubic foot),
CCF (hundred cubic
feet)

None

The register measurement units. When
a register is linked to an internal energy
source, it is set automatically. When an
external pulse source is used, the user
can select a measurement unit for the
register.

Register Source List

Source
Input

None

kWh Import

kWh Export

kvarh Import

kvarh Export

kVAh,

DI1-DI2

None

Links an energy source to the register

Multiplier

0.001 to 100.000

1.000

The multiplication factor for the energy
source.

Target

Reg#1- Reg#8

None

Defines the target billing register for the
energy source. It is set automatically.

Configuring the Daily Tariff Schedule

Configuring the Daily Tariff Schedule

Configuring the Daily Tariff Schedule

Configuring the Daily Tariff Schedule

To configure your daily tariff schedule, select Energy/TOU from the Meter Setup
menu, and then click on the TOU Daily Profiles tab.

The daily profile setup allows you to specify the daily tariff change points with a 15-
minute resolution for 4 seasons using 4 different daily schedules for each season.

To configure your daily profiles:

Select the desired season and day type.