General Technologies FF300 Fault Finder for Electrical Wiring Open / Short Circuit User Manual

Page 5

Advertising
background image

Fig.2 - Set up for tracing short or

open circuits, or location
of wiring

Fig.3 - Set up for tracing short

and open circuits, or
tracing wiring

Fig.4 - Set up for tracing open

circuits or identification
of wires

Fig.5 - Set up for upstream

tracing of open circuits
or location of wires

11- Hook up reference chart

Page 7

Page 6

For identifying wires without load connected: Connect transmitter as described in

section ‘9- Locating Open Circuits’,to the circuit to be identified. Then proceed to

scan all suspected wiring with the FF300R’s probe until the flashing and beeping is
at its maximum. In the case of tightly packed wires( bundles, conduits, etc.), it may
be necessary to spread these apart to facilitate the identification process of a particu-
lar wire.

12 - General Procedures

Short and Open Circuit operation – Differences:

The FF300 FaultFinder uses two different types of signals to trace either short or open
circuits. Understanding its differences, as explained in the following paragraphs will allow
you to make the most effective use of this versatile tool.

12.1 Working with open circuits

On detection of an open circuit, the FF300T injects a special radio signal into the

circuit, which can be picked up by the FF300R (tracer) probe.

When tracing an open circuit, keep in mind that RF (radio frequency) signals injected

in the faulty wire being traced; will be easily absorbed by any other conductor nearby.
(ie: other wires, metal frames, etc.).

Fig. 6 - Detection field when tracing open circuit with the FF300

The effect of this absorption may vary from a reduction in the tracer’s range, to a total

shielding of the signal with no detection being possible at all (See Fig. 6).

In order to avoid confusing a shielded portion of the faulty wire with the actual fault

on it, the circuit should be checked on all possible sections to confirm that no signal

is picked up on one side of the suspected faulty section.

Hint: In some cases when tracing open circuits, connecting the FF300

transmitter’s clip with the slotted wire to the faulty wire, and the clip with the

flat wire to ground or positive supply will improve the tracer’s range.

12.2

Working with short circuits (and tracing circuits)

When the FF300T detects a short circuit (or closed circuit), it injects pulses of

electrical current in the wires, which generate magnetic fields. Unlike radio signals,

magnetic fields are not easily absorbed by nearby conductors and therefore can be
picked up by the FF300R (tracer) probe in a wider range of situations (See Fig. 7).

Advertising