Figure 6, 3 gpm blend pump should be used – Lanair MXB360 User Manual

Page 15

Advertising
background image

System
Return

Check

Valve

Blend

Pump

System Supply

Pressure Reduction Valve

Backflow Preventer

System Circulator

Amtrol #720

Air Eliminator

or Equal

From City

Water Supply

Expansion

Tank

Air Separator

*

Figure 6

ATTENTION: Heating system design and burner oper-
ation must incorporate interlock to prevent burner
from firing when boiler has no system water flow.

!

*16.3 GPM Blend Pump should be used

Visit our website at: www.lanair.com

15

Section 8 - Typical Boiler Piping

System Supply

System Return

Pressure Reduction Valve

Backflow Preventer

System Circulator

Amtrol #720

Air Eliminator

or Equal

From City

Water Supply

Expansion

Tank

Air Separator

Check

Valve

Blend

Pump

Check

Valve

Blend

Pump

12”

M

ax.

12”

M

ax.

NOTES:
• Size secondary Pump GPM at gross boiler output

for a 20” drop.

• When calculating pump head, the maximum

boiler resistance for any boiler will not exceed
14” in W.C. of head

Single Boiler Piping with Blend Pump

Figure 6B

Single or Multiple Boiler Piping for Primary/Secondary Pumping