Tandard, Perating, Nstructions – Robinair RG3000 Refrigerant Recovery Machine User Manual

Page 5

Advertising
background image

5

The following instructions are for a standard or

“common” recovery procedure.

Setup Procedure

1. Place the unit on a flat, level surface.
2. Verify a clean filter screen is installed behind

the inlet fitting.

3. Connect a hose from the outlet fitting of the

unit to the liquid port on the recovery cylinder.

4. Connect a hose from the inlet fitting of the unit

to the output port of a manifold gauge set.

Promax recommends using a sight glass and a

filter / drier in this line.

5. Connect a hose from the liquid (low pressure)

side of the manifold gauge set to the liquid side

of the system being serviced.

6. Connect a hose from the vapor (high) side of

the manifold gauge set to the vapor side of the

system being serviced.

7. Verify the inlet and outlet valves on the unit are

closed.

8. Place the recovery cylinder on a scale (such as

TIF9010A) to avoid overfilling the cylinder.

S

tandard

o

Perating

i

nStructionS

Manifold

Gauge Set

System Being

Serviced

Inlet

Fitting

Outlet

Fitting

Liquid

Vapor

Scale

Recovery

Cylinder

Sight

Glass

Filter / Drier

Tech Tips

The unit will perform at its peak when voltage

entering the machine (while operating) is between

115 —122 VAC.
Lower supply voltages may result in difficulty

starting under high head pressure, reduced

performance, and / or motor overheating.
Use an outlet that does not have other applicances

(such as lights, machines, etc.) plugged into it.
Do not use an extension cord unless needed. If

an extension cord is used, it must be 14 AWG

minimum and as short as possible to reduce

voltage drops.

WARNING : A storage cylinder is full when

it reaches 80% volume. DO NOT OVERFILL. Due

to liquid expansion, the cylinder could explode

if filled to more than 80% volume, possibly

causing personal injury and equipment damage.

Liquid Port