Recycle - Manual

Follow diagram for connections to source tank. Close
LIQUID valve on tank before disconnecting blue LIQUID
hose.

For R-12 source tanks, connect 6” yellow adapter to
tank fitting before connecting hose.

Open valve on source tank.

Open GAS (vapor) valve on unit’s tank.

Press SHIFT/RESET and ENTER
at the same time.

Press 2 to transfer refrigerant.

Display shows amount transferred to tank.

Transfer stops automatically when source tank is
empty or when weight in station tank reaches 36
pounds. Display shows “CPL.”

Close source tank valve and disconnect blue
hose (or 6” yellow adapter fitting, if used) from
source tank. Reconnect blue hose to LIQUID
valve of tank.

SHIFT

RESET

ENTER

2

Changing Refrigerant Types

Move refrigerant selector switch to desired
refrigerant type

121266 (2/99)

Printed In USA

SPX ROBINAIR

SPX Corporation

1224 Robinair Way

Montpelier, OH 43543 USA

Phone 419-485-5561

Fax 419-485-8300

Source
Tank

Blue Liquid Hose