background image

4

To use the gas ballast feature...

Moisture from the A/C-R system that is carried into the pump as a vapor

tends to condense into a liquid and combine with the vacuum pump oil.

When moisture contaminates the pump oil, it reduces the pump’s ability

to reach its ultimate deep vacuum level.

The gas ballast valve purges a small amount of atmospheric air through

the exhaust chamber. This extra volume of air mixes with the vapor

from the refrigerant system to prevent condensation and to help exhaust

moisture in the form of vapor from the pump.

The gas ballast valve is located beside the handle, opposite the inlet

fitting. To use the gas ballast, start the pump and open the gas ballast

valve until the system has reached 1000–3000 microns. Close the valve

to allow the pump to pull down to its ultimate vacuum level.

The gas ballast valve may be opened or closed at any time during pump

operation. It is fully open at two turns counterclockwise.

Note: Robinair recommends the use of a thermistor vacuum gauge to

most accurately measure vacuum levels.

To shut down the pump after use...

To prolong pump life and promote easy starting, follow these procedures

for shutdown:

1. Close the manifold valve between the pump and the system.

2. Turn the Iso-Valve™ to the CLOSED position.

3. Remove the hose from the pump inlet.

4. Turn the pump power switch to OFF. Return the Iso-Valve™ to the

OPEN position for a few seconds to relieve any vacuum inside the pump.

5. Cap the inlet port to prevent any contamination or loose particles from

entering the port.