5 detector specifications, 1 compatible bases – Hochiki DRD-E User Manual
Page 12

Page 12 of 12
DRD-E Flame Detector Installation Manual
2-3-0-1376/ISS1/NOV10
© 2010 Hochiki Europe (UK) Ltd
5 Detector
Specifications
Ordering code
DRD-E
Operating voltage
15-30 Vdc (Nominal rating 24Vdc)
Standby current
70 uA at 24Vdc
Delay time
15 to 21 Second
Detection angle
90°Cone
Infrared sensitivity range
Class 1 – 0.1m
2
n-heptane at 25m
Maximum current in alarm state
40mA
Remote indicator drive(max)
20mA
Operating temperature range
-10°C to +50°C
Maximum humidity
95%RH - Non condensing (at 40°C)
Colour and case material
White Ivory ABS
Weight 125g
5.1 Compatible Bases
Order Code
Function
YBN-R/6
Common Mounting Base.
YBN-R/6SK
Common Mounting Base c/w Schottky Diode.
YBO-R/6RN
Non-Latching Relay Base
YBO-R/6RS
Latching Relay Base c/w Schottky Diode.
YBO-R/6PA
For use with compatible 2-Wire systems.
YBO-R/6R
Latching Relay Base
NOTE: Alarm control panel compatibility is required for certain base types.