5 detector specifications, 1 compatible bases – Hochiki DRD-E User Manual

Page 12

Advertising
background image

Page 12 of 12

DRD-E Flame Detector Installation Manual

2-3-0-1376/ISS1/NOV10

© 2010 Hochiki Europe (UK) Ltd

5 Detector

Specifications

Ordering code

DRD-E

Operating voltage

15-30 Vdc (Nominal rating 24Vdc)

Standby current

70 uA at 24Vdc

Delay time

15 to 21 Second

Detection angle

90°Cone

Infrared sensitivity range

Class 1 – 0.1m

2

n-heptane at 25m

Maximum current in alarm state

40mA

Remote indicator drive(max)

20mA

Operating temperature range

-10°C to +50°C

Maximum humidity

95%RH - Non condensing (at 40°C)

Colour and case material

White Ivory ABS

Weight 125g

5.1 Compatible Bases

Order Code

Function

YBN-R/6

Common Mounting Base.

YBN-R/6SK

Common Mounting Base c/w Schottky Diode.

YBO-R/6RN

Non-Latching Relay Base

YBO-R/6RS

Latching Relay Base c/w Schottky Diode.

YBO-R/6PA

For use with compatible 2-Wire systems.

YBO-R/6R

Latching Relay Base

NOTE: Alarm control panel compatibility is required for certain base types.