Multiple boiler manifold piping – HTP EL-399 User Manual

Page 24

Advertising
background image

24

LP- 293 REV. 5.20.14

The chart below represents the various system design temperature rise through the boiler along with their respective flows and friction
loss, which will aid in circulator selection.

The chart on the following page represents the combined flow rates and pipe sizes when using multiple boilers to design the manifold
system for the primary circuit. To size, simply add up the number of boilers and the required flow rates for the system design
temperature.

Example: (5) EL-220 Boilers® with a design of 20°

Δt degree temperature rise with each boiler having an individual flow rate of 22 GPM.

To correctly size the manifold feeding these (5) boiler

s you would need a pipe size of 4”.

MULTIPLE BOILER MANIFOLD PIPING

Flow Rate (GPM)

16

22

24

30

32

33

40

44

45

48

50

55

60

66

75

80

85

88

90

100

110

Pipe Dia. (Inches)

2

2

2

2

2

3

3

3

3

3

3

4

Table 6

Figure 10

MULTIPLE BOILER MANIFOLD PIPING

Flow Rate (GPM) 120

132

150

160

170

179

200

210

239

240

250

255

300

340

350

400

425

510

595

680

Pipe Dia. (In.)

4

4

4

4

4

4

4

4

5

5

5

5

5

5

5

5

5

6

6

6

Table 7

0

1

2

3

4

5

6

0

50

100

150

200

250

Pi

p

e

Di

am

e

te

r Si

ze

(In

ch

e

s)

Combined Boiler Water Flow (GPM)

Multiple Boiler Manifold Piping

Flow Rate

23

GPM

24 GPM

25 GPM

26 GPM

27 GPM

28 GPM

29 GPM

30 GPM

31 GPM

32 GPM

33 GPM

34 GPM

35 GPM

36 GPM

37

GPM

38 GPM

39 GPM

EL-80

*

*

*

*

*

*

*

*

*

*

*

*

*

*

*

*

*

EL-110

*

*

*

*

*

*

*

*

*

*

*

*

*

*

*

*

*

EL-150

*

*

*

*

*

*

*

*

*

*

*

*

*

*

*

*

*

EL-220

21’

23’

24’

*

*

*

*

*

*

*

*

*

*

*

*

*

*

EL-299

EL-301

16.5’

18’

20’

22’

24’

26’

29’

33’

36’

*

*

*

*

*

*

*

*

EL-399

*

*

*

12.9’

13.6’

14’

15.7’

17’

18’

19.4’

21’

22.5’

26’

28’

31’

34’

39’

Table 4

– NOTE:

*Do not operate boiler at these flow settings as it will damage the heat exchanger or related components.

Table 5

SYSTEM TEMPERATURE RISE CHART

Model

20°Δt

25°Δt

30°Δt

Ft / Friction

Flow Rate

Ft / Friction

Flow Rate

Ft / Friction

Flow Rate

EL-80

17’

8 GPM

10’

6.6 GPM

7’

5.3 GPM

EL-110

25’

11 GPM

17’

9.1 GPM

12’

7.3 GPM

EL-150

27’

15 GPM

17’

12.5 GPM

12’

10 GPM

EL-220

19’

22 GPM

13’

18.3 GPM

12’

14.6 GPM

EL-299

EL-301

29’

29 GPM

18’

24.5 GPM

13’

20 GPM

EL-399

39’

39 GPM

19’

32.5 GPM

13’

26 GPM