JuiceGoose JG 11 Series User Manual

Page 2

Advertising
background image

SAFETY PRECAUTIONS
The JG 11.0-20A and JG 11.0-15A (JG11) are designed to operate with 120VAC, 60 Hz.
Operation with 220 or 240 volts will cause damage and possibly cause personal injury.

CAUTIONS
1. The JG11 must be grounded. Defeating the unit’s grounding capability could
create a hazard.
2. There are no user serviceable parts inside. Do not attempt service yourself. Contact
Juice Goose as directed in this manual if service is required.
3. Do not expose the JG11 to moisture. Avoid severe physical impacts to the unit.

DISCLAIMER
Juice Goose shall under no circumstances be held responsible for any loss, damage or in-
jury resulting from the use of the JG11 in a manner inconsistent with any of the proce-
dures outlined in this document. The user is responsible for determining whether this
product is appropriate for the intended application.

Juice Goose is not responsible for any indirect, secondary or ancillary loss or damage,
including personal injury, loss of or damage to property or loss of income resulting from
the operation or failure of this unit.

FRONT PANEL

Lighted Power On/Off Switch – This switch controls power to all 8 outlets on the back
of the chassis.

AC Outlet – This outlet is always on when the power cord is attached to an active power
source.

REAR PANEL

AC Outlets – These 10 outlets (NEMA 5-15R) are rated for current loads up to 15 amps
per outlet at 120 volts. Although the JG11.0-20A is rated for a total current load of 20
amps, each outlet’s rating is limited to 15 amps. The JG11.0-15A is rated for a total cur-
rent load of 15 amps with each outlet’s rating limited to 15 amps.

Power Cord – The power cord has a third pin safety ground connector. Do not defeat this
feature. Doing so could subject user to a hazardous condition.

POWER CORD

The JG11.0-20A is equipped with a 12 gauge power cord that measures slightly less than
15 feet in length. This cord has a NEMA5-20P plug that requires a 20 amp receptacle to
be connected to a power source. It can not be connected to a 15 amp receptacle.
The JG11.0-15A is equipped with a 12 gauge power cord that measures slightly less than
15 feet in length. This cord has a NEMA5-15P plug and can be connected to a 15 amp
receptacle.

INTERNAL PROTECTION COMPONENTS

The JG11 Series products have a Basic Level of AC power protection consisting of fast
acting metal oxide varistors between hot, neutral and ground and a line capacitor between
hot and neutral to reduce high frequency line noise and AC line surges.

Advertising