Ds−2b, Recommended switch settings by function, Fine adjustment for efficient operation – King Electric DS-2B User Manual

Page 4: Manual override switch operation, Typical load wiring

Advertising
background image

The relay inside the DS-2B acts as a switch. While not as convenient as directly supplying power for the
load this allows you to operate the DS-2B from one voltage while controlling a load of a different voltage
without adding an external relay or contactor. For example, the DS-2B can be powered from 120VAC but
can directly control a 24VAC signal for a boiler system or 240VAC for heating wire. The following diagrams
show some possible wiring schemes for connecting the DS-2B to your load. Your load may be a direct
connection to heat cable, a heater, a contactor coil, or a control voltage. For clarity the safety GROUND
leads are not shown.

Recommended Switch Settings by Function

Function

Trigger

Delay

LTC

DEL

RAIN

SNOW

Snow sensor w\o LTC

TT>AT

2 Min

OFF

OFF

OFF

ON

Snow sensor w\LTC

TT>AT>15

°F

2 Min

ON

OFF

OFF

ON

Snow controller w\o LTC

TT>AT

30-90 Min

OFF

ON

OFF

ON

Snow controller w\LTC

TT>AT>15

°F

30-90 Min

ON

ON

OFF

ON

Precipitation sensor

Not Used

2 Min

X

OFF

ON

ON

Precipitation controller

Not Used

30-90 Min

X

ON

ON

ON

Rain sensor

AT>TT

2 Min

X

OFF

ON

OFF

Rain controller

AT>TT

30-90 Min

X

ON

ON

OFF

LT thermostat w\o LTC

TT>AT

2 Min

OFF

X

OFF

OFF

LT thermostat w\LTC

TT>AT>15

°F

2 Min

ON

X

OFF

OFF

Fine Adjustment for Efficient Operation

The DS-2B is shipped with the TEMP and DEL adjustments in the center position, representing 39°F
(3.9°C) and 30 minutes of Delay-Off time respectively. Depending on local conditions the user may find
that fine adjustment of the controls may provide more satisfactory operation. If the sensor does not trigger
during very wet snows the trigger temperature may need to be adjusted higher. Conversely, if the user
notices false triggers during cold rains that do not freeze, the trigger temperature may need to be lowered.
The Delay-Off time can also be adjusted to provide clean melt-off without excessive running time. Fine
adjustment can both save operating expense and provide more reliable operation. However, to keep
reliability high, always make adjustments in small increments.

Always Use Care When Replacing The Front Cover

Be sure the front cover gasket is not pinched or rolled. Do not overtighten the front cover screws.

Manual Override Switch Operation

An override switch mounted on the side is provided for testing and special operational requirements.
Placing the switch in the “Automatic” position will allow the sensor to operate normally, activating the
controlled equipment as needed. Placing the switch in “Manual On” will close the load relay, activating the
controlled equipment. The “Standby/Reset” position prohibits triggering of the unit, clears any active delay
timer, and opens the load relay. In order to reduce excessive runtime for the heater the “Manual On”
mode will remain in effect for a maximum of 40 hours, then return to “Automatic” mode even if the
switch is still in the “Manual On” position.
You may put the DS-2B back into “Manual On” mode by
switching to “Automatic”, then back to “Manual On”. This will restart the 40 hour timer.

If the override switch is placed in “Manual On” for less than 2 seconds, then switched back to
“Automatic” the controller will execute one delay off cycle
. This can be used to clear a frost or hail
buildup without the danger of leaving the system in a continuous “Manual On” condition. “Standby/Reset”
can still be used to clear this delay off cycle.

4

Typical Load Wiring

The two load leads are N.O. contacts and do not supply power directly to your load

NEUTRAL BUS BAR

20A

LINE/L1

NEU/L2

YELLOW

YELLOW

LOAD

DS−2B

SWITCHED 120VAC

NEUTRAL

LOAD CENTER

20

A

LINE/L1

NEU/L2

YELLOW

YELLOW

LOAD

DS−2B

SWITCHED 240VAC

LOAD CENTER

120VAC In, 120VAC Load, Heat Cable or Similar (Strap DS-2B for 120VAC Power)

240VAC In, 240VAC Load, Heat Cable or Similar (Strap DS-2B for 240VAC Power)