Hfc134a service information, Replacement service compressor, Warning – Amana Bottom Mount Refrigerator User Manual

Page 15

Advertising
background image

November 1996

15

RS1200001

HFC134a Service Information

Replacement Service Compressor

HFC134a service compressors will be charged with
ester oil and pressurized with dry nitrogen. Before
replacement compressor is installed, pull out 1 rubber
plug. A pop from pressure release should be heard. If
a pop sound is not heard, do not use compressor.
Positive pressure in compressor is vital to keep
moisture out of ester oil. Do not leave compressor
open to atmosphere for more than 10 minutes.

Compressor Testing Procedures
• Refer to “Temperature and Relationship Chart” for

operating watts, test points, and temperature
relationship test.

• Temperature testing is accomplished by using 3 lead

thermocouple temperature tester in specific locations.
Test point T-1 is outlet on evaporator coil and T-2 is
inlet. Test point T-3 is suction tube temperature
midway between where armaflex ends and suction
port of compressor (approximately 12 inches from
compressor).

• Thermocouple tips should be attached securely to

specified locations.

• Do not test during initial pull down. Allow one off cycle

or balanced temperature condition to occur before
proceeding with testing.

• Refrigerator must operate minimum of 20 minutes

after thermocouples are installed.

• Turn control to colder to obtain required on time.
• Wattage reading must be recorded in conjunction with

temperature test to confirm proper operation.

• Suction and head pressures are listed on

“Temperature and Relationship Chart” Normally these
are not required for diagnosis but used for
confirmation on systems which have been opened.

Refrigerant Charge
Refrigerant charge in all capillary tube systems is
critical and exact amount is required for proper
performance. Factory charges are shown on serial
plate. Do not use refrigerant other than shown on
serial plate.

Leak Testing
Undetected leaks lead to repeated service calls and
eventually result in system contaminations,
restrictions, and burned out compressors.

After recharging, sealed system must be thoroughly
tested for leaks. If a very small leak is difficult to
isolate, coat area with soap suds and observe
location of bubbles.

To avoid death or severe personal injury, never
use oxygen, air or acetylene for pressure testing
or cleanout of refrigeration system. Use of
oxygen, air, or acetylene may result in violent
explosion. Oxygen may explode on contact with
oil and acetylene will spontaneously explode
when under pressure.

WARNING

Evacuation and Charging

Vacuum Pump

.6 cm Copper

Tubing

Compressor

Compressor
Process
Tube

Charging Hose

Thermistor

Vacuum Gauge

Low Side Gauge

E

Valve

B

D

Valve

High Side Gauge

Charging Hose

Drier/Process Tube

F

Valve

Charging

Cylinder

C

A